REMOVAL

PROCEDURE

S E R V I C E   M A N U A L

Outdoor Unit

Inverter

Multi Type

4/5/6 HP Class

Si341305E

Содержание RXYSQ4P7Y1B

Страница 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Inverter Multi Type 4 5 6 HP Class Si341305E...

Страница 2: ...Service Manual Removal Procedure Outdoor Unit Applicable Models zHeat Pump RXYSQ4P7Y1B RXYSQ5P7Y1B RXYSQ6P7Y1B...

Страница 3: ...Si341305E Removal Procedure 1 Table of Contents 1 Procedure to Remove Outside Panels 2 2 Procedure to Remove Propeller Fan and Fan Motor 5 3 Procedure to Remove Compressor 7...

Страница 4: ...then remove the panel after pushing it downward to release the hook To remove the front panel for piping cover remove its 1 screw To remove the side panel for piping cover remove 4 screws of the side...

Страница 5: ...ts 4 screws and releasing its 4 hooks Remove the front panel 1 after removing its 7 screws and pushing it upward On the rear side of the front panel 1 a reinforce plate is attached Be careful not to l...

Страница 6: ...move the heat exchanger cover after releasing its 3 hooks with a minus driver 9 Remove the outdoor air thermistor after pulling it to the near side and sliding to the right 10 The figure in the right...

Страница 7: ...it for 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points Remove the discharge grill front panel and front panel for piping cover according to the...

Страница 8: ...ad wires are not fixed by using the clamp material it may always damage the lead wire because the lead wires twined around the fan When mounting the propeller fan make the D cut correspond to the hole...

Страница 9: ...trical component and compressor fixing panel according to the Procedure to Remove Outside Panels 1 Pull off the lead wire of compressor 1 Open upward the sound insulation for the terminal cover 2 Remo...

Страница 10: ...on for the compressor 5 Remove the crankcase heater under the compressor Pull the spring to trip the catch 6 Remove the 3 fixing bolts of the compressor You can see the far side fixing bolts when the...

Страница 11: ...ing a pipe cutter before replacing with a new compressor 7 Cut off the suction pipe discharge pipe and unloader pipe of compressor with a pipe cutter 3 places Step Procedure Points Compressor Discharg...

Страница 12: ...Revision History Month Year Version Revised contents 07 2013 Si341305E First edition...

Страница 13: ...kage electrical shock fire or explosion z Read the User s Manual carefully before using this product The User s Manual provides important safety instructions and warnings Be sure to follow these instr...