• Outdoor Unit • RXYSQ-P8V1
2
• VRV Systems • RXYSQ-P8V1
4
2
Specifications
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Connection pipes; Quantity : 3;
Fan motor 2
Model
Brushless DC motor
Speed
Cooling Nom.
rpm
815
Heating Nom.
rpm
785
805
Drive
Direct drive
Output
W
70
Sound power level
Cooling
Nom.
dBA
66
67
69
Sound pressure level
Cooling
Nom.
dBA
50
51
53
Heating
Nom.
dBA
52
53
55
Operation range
Cooling
Min.~Max.
°CDB
-5~46
Heating
Min.~Max.
°CWB
-20~15.5
Refrigerant
Type
R-410A
Charge
kg
4.0
Control
Expansion valve
Circuits
Quantity
1
Refrigerant oil
Type
Daphne FVC68D
Charged volume
l
1.5
Piping connections
Liquid
Type
Flare connection
OD
mm
9.52
Gas
Type
Flare connection (VRV®) / Braze connection (RA)
Braze connection
OD
mm
15.9 (6) / 19.1 (7)
19.1
Drain
Quantity
3
OD
mm
26x3
Heat insulation
Both liquid and gas pipes
Piping length
OU -
BP
Total
m
55
BP - IU Max.
m
15
Total
m
60
80
90
Total piping length
System Actual
m
300 / 115
300 / 135
300 / 145
Level difference
OU - IU Outdoo
r unit in
highest
position
m
-
Indoor
unit in
highest
position
m
-
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
HPS
02
Fan motor thermal protection
03
Inverter overload protector
04
PC board fuse
PED
Category
Category I
2-2 Electrical Specifications
RXYSQ4P8V1
RXYSQ5P8V1
RXYSQ6P8V1
Power supply
Name
V1
Phase
1N~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current
Nominal running
current (RLA) - 50Hz
Cooling
A
15.9
20.2
22.2
2-1 Technical Specifications
RXYSQ4P8V1
RXYSQ5P8V1
RXYSQ6P8V1
Содержание RXYSQ-P8V1
Страница 1: ...Air Conditioning Technical Data VRVIII S heat pump EEDEN14 100 RXYSQ P8V1 ...
Страница 2: ......
Страница 11: ...3 4 VRV Systems RXYSQ P8V1 9 Outdoor Unit RXYSQ P8V1 4 Capacity tables 4 3 Capacity Correction Factor ...
Страница 15: ...3 6 VRV Systems RXYSQ P8V1 13 Outdoor Unit RXYSQ P8V1 6 Centre of gravity 6 1 Centre of Gravity 4D052604B ...
Страница 20: ... Outdoor Unit RXYSQ P8V1 10 VRV Systems RXYSQ P8V1 18 10 Sound data 10 2 Sound Pressure Spectrum Cooling ...
Страница 21: ...3 10 VRV Systems RXYSQ P8V1 19 Outdoor Unit RXYSQ P8V1 10 Sound data 10 3 Sound Pressure Spectrum Heating ...
Страница 24: ... Outdoor Unit RXYSQ P8V1 12 VRV Systems RXYSQ P8V1 22 12 Operation range 12 1 Operation Range 3D045713F ...