Daikin RXYSCQ4TMV1B Скачать руководство пользователя страница 9

5 Preparation

Installer and user reference guide

9

5TMV1B
VRV IV-S system air conditioner
4P404224-1 – 2015.03

PC configurator cable (EKPCCAB)

You  can  make  several  commissioning  field  settings  through  a
personal  computer  interface.  For  this  option  EKPCCAB  is  required
which  is  a  dedicated  cable  to  communicate  with  the  outdoor  unit.
The 

user 

interface 

software 

is 

available 

on 

http://

www.daikineurope.com/support-and-manuals/software-downloads/

.

5

Preparation

5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.

It contains information about:

▪ Preparing the installation site

▪ Preparing the refrigerant piping

▪ Preparing the electrical wiring

5.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of  construction  works  (e.g.  grinding  works)  where  a  lot  of  dust  is
created, the unit must be covered.

Choose the installation location with sufficient place for carrying the
unit in and out of the site.

5.2.1

Installation site requirements of the
outdoor unit

INFORMATION

Also read the following requirements:

▪ General  installation  site  requirements.  See  the

"General safety precautions" chapter.

▪ Service  space  requirements.  See  the  "Technical  data"

chapter.

▪ Refrigerant 

piping 

requirements 

(length, 

height

difference). See further in this "Preparation" chapter.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

NOTICE

The  equipment  described  in  this  manual  may  cause
electronic  noise  generated  from  radio-frequency  energy.
The  equipment  complies  to  specifications  that  are
designed  to  provide  reasonable  protection  against  such
interference.  However,  there  is  no  guarantee  that
interference will not occur in a particular installation.

It  is  therefore  recommended  to  install  the  equipment  and
electric  wires  keeping  proper  distances  away  from  stereo
equipment, personal computers, etc.

b

c

f

d

d

a

c

b

e

(mm)

a

Personal computer or radio

b

Fuse

c

Earth leakage protector

d

User interface

e

Indoor unit

f

Outdoor unit

In  places  with  weak  reception,  keep  distances  of  3  m  or  more  to
avoid  electromagnetic  disturbance  of  other  equipment  and  use
conduit tubes for power and transmission lines.

▪ Select a place where rain can be avoided as much as possible.

▪ Take  care  that  in  the  event  of  a  water  leak,  water  cannot  cause

any damage to the installation space and surroundings.

▪ Choose a location where the hot/cold air discharged from the unit

or the operation noise, will NOT disturb anyone.

▪ Heat  exchanger  fins  are  sharp  and  injury  is  possible.  Choose  an

installation  location  where  there  is  no  risk  for  injury  (especially  in
areas where children play).

Do NOT install the unit in the following places:

▪ Sound sensitive areas (e.g. near a bedroom and the like), so that

the operation noise will cause no trouble.
Note:  If  the  sound  is  measured  under  actual  installation
conditions,  the  measured  value  might  be  higher  than  the  sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

It  is  NOT  recommended  to  install  the  unit  in  the  following  places
because it may shorten the life of the unit:

▪ Where the voltage fluctuates a lot

▪ In vehicles or vessels

▪ Where acidic or alkaline vapour is present

Seaside  installation.

  Make  sure  the  outdoor  unit  is  NOT  directly

exposed  to  sea  winds.  This  is  to  prevent  corrosion  caused  by  high
levels of salt in the air, which might shorten the life of the unit.

Install the outdoor unit away from direct sea winds.

Example: 

Behind the building.

b

c

a

Содержание RXYSCQ4TMV1B

Страница 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B...

Страница 2: ...e pipe end 17 6 4 6 To braze the pipe end 17 6 4 7 Using the stop valve and service port 17 6 4 8 To connect the refrigerant piping to the outdoor unit 18 6 4 9 To connect the refrigerant branching ki...

Страница 3: ...Symptom The system does not operate 55 20 2 2 Symptom Fan operation is possible but cooling and heating do not work 56 20 2 3 Symptom The fan strength does not correspond to the setting 56 20 2 4 Sym...

Страница 4: ...tall or operate the unit contact your dealer NOTICE Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks fire or other damage to the equip...

Страница 5: ...re is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It states the type o...

Страница 6: ...ake sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector Install power cables at least 1 metre away from telev...

Страница 7: ...to be brought in 3 2 Outdoor unit 3 2 1 To unpack the outdoor unit 1 2 3 2 2 To handle the outdoor unit Carry the unit slowly as shown CAUTION To avoid injury do NOT touch the air inlet or aluminum fi...

Страница 8: ...oor units and is intended for R410A use only For an overview which units are available you can consult the product catalogue for VRV IV S An overview is given indicating the allowed combinations of in...

Страница 9: ...o guarantee that interference will not occur in a particular installation It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment pe...

Страница 10: ...n cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal minimum height 150 mm c Prevailing win...

Страница 11: ...s installed In a case such as the following calculate the volume of A B as a single room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there...

Страница 12: ...r the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 6 7 3 To determine the additional refrigerant amount on page 21 A Piping...

Страница 13: ...erence The piping lengths and height differences must comply with the following requirements Two patterns will be discussed Outdoor with 100 VRV DX indoor units Outdoor with 100 RA DX indoor units Req...

Страница 14: ...tems with input current 16 A and 75 A per phase 5 4 2 Safety device requirements The power supply must be protected with the required safety devices i e a main switch a slow blow fuse on each phase an...

Страница 15: ...e outdoor unit 3 Providing drainage 4 Preventing the outdoor unit from falling over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See Preparing installation...

Страница 16: ...nvolves Connecting the refrigerant piping to the outdoor unit Connecting refrigerant branch kits Connecting the refrigerant piping to the indoor units see the installation manual of the indoor units I...

Страница 17: ...re the pipe Set exactly at the position as shown in the following illustration A Conventional flare tool Flare tool for R410A clutch type Clutch type Ridgid type Wing nut type Imperial type A 0 0 5 mm...

Страница 18: ...handle the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service po...

Страница 19: ...ered on the expansion valves will initialise This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explai...

Страница 20: ...t for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap wa...

Страница 21: ...sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minutes after the in...

Страница 22: ...erant charge mode instructions Charging refrigerant in manual additional refrigerant charge mode The remaining additional refrigerant charge can be charged by operating the outdoor unit by means of th...

Страница 23: ...a Field power supply with earth leakage protector b Main switch c Earth connection d Outdoor unit e Indoor unit f User interface g Power supply wiring sheathed cable 230 V h Transmission wiring sheat...

Страница 24: ...After finishing the electrical work confirm that each electrical component and terminal inside the electrical components box is connected securely Make sure all covers are closed before starting up t...

Страница 25: ...ring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct proper reattachment of th...

Страница 26: ...htening torque does NOT exceed 4 1 N m 5 7 Configuration 7 1 Overview Configuration This chapter describes what you have to do and know to configure the system after it is installed It contains inform...

Страница 27: ...indoor unit is installed 7 LEDs display The display gives feedback about the field settings which are defined as Mode Setting Value H1P Shows the mode H2P H7P Shows the settings and values represented...

Страница 28: ...mode 2 BS1 5 s 3 Select setting 8 X depends on the setting that you want to select BS2 X binary 8 Action Button display 4 Select value 4 8 C a Display the current value b Change to 4 X depends on the...

Страница 29: ...rface they can be checked again through this monitoring settings For the content or reason behind the malfunction code see 11 3 Solving problems based on error codes on page 36 where most relevant mal...

Страница 30: ...e level of operation Depending on the chosen level the noise level will be lowered The start and stop moments for this function are defined under setting 2 26 and 2 27 default Deactivated Level 1 Leve...

Страница 31: ...ral patterns are available and explained below Modify the parameters to the needs of your building and to realize the best balance between energy consumption and comfort No matter which control is sel...

Страница 32: ...sed in conjunction with setting 2 9 Quick Overshoot during heating operation or undershoot during cooling operation is allowed compared to the requested refrigerant temperature in order to achieve the...

Страница 33: ...porating temperature Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful 7 3 4 Example Automatic mode...

Страница 34: ...abnormal noises and vibrations when starting up the unit Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 6 8 Connecting the elect...

Страница 35: ...trol Cooling stable condition Communication check Stop valve check Pipe length check Pump down operation Unit stop INFORMATION During the test operation it is not possible to stop the unit operation f...

Страница 36: ...essure leading to worse performance 10 4 About service mode operation Refrigerant recovery operation vacuuming operation is possible by applying setting 2 21 Refer to 7 2 Making field settings on page...

Страница 37: ...nction R2T open circuit short circuit A1P X12A Check connection on PCB or actuator Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperatu...

Страница 38: ...he piping and wiring of the specified indoor unit are not connected correctly to the outdoor unit Open the stop valve on both the gas and liquid side Confirm that the piping and wiring of the specifie...

Страница 39: ...in mm 40 490 485 495 170 620 150 60 101 30 460 30 37 52 823 940 88 60 19 100 151 52 102 118 59 62 216 130 20 98 21 89 32 17 69 17 104 53 95 289 313 53 95 19 80 3D089312 j b h i g a f e d f c f a Gas p...

Страница 40: ...250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB HD HD HU 250 1000 1000 500 H...

Страница 41: ...A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lowe...

Страница 42: ...id e Stop valve gas f Service port refrigerant charge g Service port high pressure h Switch box i Cable tie mountings to fix the field wiring with cable ties to ensure stress relief j Accumulator k Fa...

Страница 43: ...exchanger i Service port high pressure j Muffler k Check valve l Compressor accumulator m Capillary tube n Service port refrigerant charge o Accumulator M1C Compressor M1F Fan motor R1T Thermistor ai...

Страница 44: ...N RED ORG YLW X81A Z7C N 2 Z5C N 1 Z6C N 2 TO OUT D TO IN D Z7C N 1 GRN Z5C N 3 X2M F1 F2 F1 F2 X99A FRONT DETAIL OF ELECTRICAL COMPONENT BOX BACK Position of compressor terminal NOTE 6 NOTE 7 OUTDOOR...

Страница 45: ...L1R L3R Reactor M1C Motor compressor M1F Motor fan PS Switching power supply R1 R2 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction 1 R4T Thermistor heat exchanger de icer...

Страница 46: ...Heating nominal b Capacity 12 1 kW 14 0 kW COP 3 81 3 58 PED Category 1 Most critical part Compressor PS V 167 bar l Maximum number of indoor units connected c 64 Heat exchanger Type Cross fin Treatm...

Страница 47: ...50 Hz Voltage 220 240 V Current Nominal running current RLA a 19 0 A Starting current MSC b MCA Minimum circuit amps MCA c 29 1 A Maximum fuse amps MFA d 32 A Total overcurrent amps TOCA e 29 1 A Full...

Страница 48: ...s needs to be within the specified range The connection ratio CR 50 CR 130 HP class of outdoor unit 50 minimum CR VRV DX 80 minimum CR RA DX 100 nominal CR 130 maximum CR 4 50 80 100 130 5 62 5 100 12...

Страница 49: ...erface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g Us...

Страница 50: ...creases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor units The indoor unit will stop fan operation the refrigerant cycle will reverse and energy fr...

Страница 51: ...ect expansion DX indoor unit d User interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air R...

Страница 52: ...s equipped with advanced energy saving functionality Depending on the priority emphasises can be put on energy saving or comfort level Several parameters can be selected resulting in the optimal balan...

Страница 53: ...may be required depending on the applicable legislation Please contact your installer for more information WARNING The refrigerant in the air conditioner is safe and normally does not leak If the ref...

Страница 54: ...table indicates main components Refer to your maintenance and inspection contract for more details The table indicates recommended intervals of replacement cycles However in order to keep the unit ope...

Страница 55: ...ir thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activate...

Страница 56: ...or U5 and stops but then restarts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication...

Страница 57: ...the product and or operates the product Applicable legislation All international European national and local directives laws regulations and or codes that are relevant and applicable for a certain pro...

Страница 58: ......

Страница 59: ......

Страница 60: ...4P404224 1 2015 03 Copyright 2015 Daikin...

Отзывы: