SiUS34-801A_b
Field Setting
VRVIII R-410A Heat Recovery 60Hz
243
12.1.2 Setting by Dip Switches
(1) Factory setting of initial PC board.
Do not make any changes to the factory settings of the DIP switches on the control PC board.
*
For detail of the setting procedure, refer to information on the following pages.
While the PC board assembly is replaced, the [
U3
] malfunction (Test run not carried out yet)
code is displayed. In this case, carry out the test run again.
If the [
PJ
], [
UA
], or [
U7
] malfunction code is displayed, recheck for DIP switch settings.
After completing rechecking of settings, turn ON the power supply again.
1 2 3 4
1 2 3 4
ON
OFF
ON
OFF
DS1
DS2
Status of DIP switches
: Represents the factory setting positions
of the switches.
Setting at replacement by spare PC board
Caution
DIP switch Setting after changing the main PC board(A1P) to spare parts PC board
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main PC board (A1P) to spare parts PC board, please carry out the
following setting.
DIP Switch Detail
DS No.
Item
Contents
DS1-2
Power supply
specification
ON
200V class (220V)
OFF (Factory
setting of spare
PC board)
400V class (380V)
DS1-3
Except
Multiple
use
Cooling only/Heat-
pump setting
ON
Cooling only setting
OFF (Factory
setting of spare
PC board)
Heat pump setting
DS1-4
Unit allocation
setting
ON
Make the following settings according to allocation of
unit. (All models are set to OFF at factory.)
DS2-1
OFF (Factory
setting of spare
PC board)
DS2-2
Model setting
Make the settings according to models of outdoor units. (All
models are set to OFF at factory.)
* Refer to following pages for setting detail.
DS2-3
DS2-4
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
ON
OFF
Initial conditions of dip switches
Multiple use
or Single
use (Main)
Single use
(Sub)
Domestic
Japan
Overseas
General
Europe
U.S.A.
DS1-4
DS1-3
OFF
OFF
ON
ON
DS2-1
DS1-4
OFF
ON
OFF
ON
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...