Test Operation
SiUS34-801A_b
226
VRVIII R-410A Heat Recovery 60Hz
10.2.5 Checking of Device and Installation Conditions
Be sure to check the following:
For those doing electrical work
1. Make sure there is no faulty transmission wiring or loosening of a nut.
2. Make sure there is no faulty power wiring or loosening of a nut.
3. Has the insulation of the main power circuit deteriorated?
Measure the insulation and check to ensure that the insulation is above the regular value in
accordance with relevant local and national regulations.
For those doing pipe work
1. Make sure piping size is correct.
2. Make sure insulation work is done.
See
10.2.4 Pipe Insulation
.
3. Make sure there is no faulty refrigerant piping.
10.2.6 Additional Refrigerant Charge and Check Operation
The outside unit is charged with refrigerant when shipped from the factory, but depending on the
size and length of the piping when installed, it may require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter and
then carry out the check operation.
10.2.6.1
Before working
[About the refrigerant tank]
Check whether the tank has a siphon pipe before charging and place the tank so that the
refrigerant is charged in liquid form.
(See the figure below.)
NOTE:
Always use the proper refrigerant (R-410A). If charged with refrigerant containing an improper
material, it may cause an explosion or accident.
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition to
change, which may prevent normal operation.
[Shutoff valve operation procedure]
When operating the shutoff valve, use the following procedures:
With siphon pipe
Other tanks
Stand the tank
u
pright and charge.
(The siphon pipe goes all the
w
ay inside,
so the tank does not need to
b
e p
u
t
u
pside-do
w
n to charge in li
qu
id form.)
Stand the tank upside-down and charge.
Содержание RXYQ96PYDN
Страница 15: ...SiUS34 801A_b xiv...
Страница 23: ...Model Selection SiUS34 801A_b 8 General Information...
Страница 133: ...Field Settings SiUS34 801A_b 118 VRVIII R 410A Heat Pump 60Hz...
Страница 254: ...SiUS34 801A_b Test Operation VRVIII R 410A Heat Recovery 60Hz 239 R 410A Label R 410A Label...
Страница 329: ...Field Setting SiUS34 801A_b 314 Indoor Unit...
Страница 340: ...SiUS34 801A_b Troubleshooting by Remote Controller Troubleshooting 325...
Страница 489: ...Piping Diagrams SiUS34 801A_b 474 Appendix 1 Piping Diagrams 1 1 Outdoor Unit Heat Pump 460V RXYQ72 96 120PYDN 3D058636A...
Страница 490: ...SiUS34 801A_b Piping Diagrams Appendix 475 Heat Pump 230V RXYQ72 96 120PTJU 3D058636A...
Страница 491: ...Piping Diagrams SiUS34 801A_b 476 Appendix Heat Pump 230V RXYQ144PTJU 3D058640...
Страница 492: ...SiUS34 801A_b Piping Diagrams Appendix 477 Heat Recovery 460V REYQ72 96 120PYDN 3D058639A...
Страница 493: ...Piping Diagrams SiUS34 801A_b 478 Appendix Heat Recovery 460V REMQ72PYDN 3D058637A...
Страница 494: ...SiUS34 801A_b Piping Diagrams Appendix 479 Heat Recovery 460V REMQ96 120PYDN 3D058638A...
Страница 495: ...Piping Diagrams SiUS34 801A_b 480 Appendix Heat Recovery 230V REYQ72 96 120PTJU 3D058639A...
Страница 496: ...SiUS34 801A_b Piping Diagrams Appendix 481 Heat Recovery 230V REYQ144PTJU 3D058640...
Страница 497: ...Piping Diagrams SiUS34 801A_b 482 Appendix Heat Recovery 230V REMQ72PTJU 3D058637A...
Страница 498: ...SiUS34 801A_b Piping Diagrams Appendix 483 Heat Recovery 230V REMQ96 120PTJU 3D058638A...
Страница 501: ...Piping Diagrams SiUS34 801A_b 486 Appendix 1 3 BS Unit 4D057985A...
Страница 537: ...Piping Installation Point SiUS34 801A_b 522 Appendix...
Страница 543: ...Pressure Sensor SiUS34 801A_b 528 Appendix...
Страница 559: ...Precautions for New Refrigerant R 410A SiUS34 801A_b 544 Precautions for New Refrigerant R 410A...
Страница 563: ...SiUS34 801A_b iv Index...