background image

English

16

Use an insulated rod to operate the push buttons via the EL. 
COMPO. BOX’s inspection door.
There is a risk of electric shock if you touch any live parts, since this 
operation must be performed with the power on.

CAUTION

Make sure to use the protect tool (protective groves and goggles) 
when charging the refrigerant.

Due to a danger of liquid hammer, the refrigerant must not be charged 
over the allowable maximum amount when charging the refrigerant.

Do not perform the refrigerant charging operation under working for 
the indoor unit.

When opening the front panel, make sure to take caution to the fan 
rotation during the working.
After the outside unit stops operating, the fan may keep rotation for a 
while.

NOTE

If operation is performed within 12 minutes after the indoor and out-
side units are turned on, H2P will be lit on and the compressor will 
not operate.
Check the LED display indicate as shown below.

In order to ensure uniform refrigerant distribution, it may take up to 
around 10 minutes for the compressor to start up after the unit start-
ing operating. This is not a malfunction.

The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the unit’s internal piping is 
already charged with refrigerant, so be careful when connecting the 
charge hose.

After adding the refrigerant, make sure to close the lid of the refrig-
erant charging port.
The tightening torque for the lid is 8.48 to 10.3 ft · lbf.

See [Shutoff valve operation procedure] in chapter 11-1 for details 
on how to handle shutoff valves.

When done or when pausing the refrigerant charging operation, close 
the valve of the refrigerant tank immediately.
The refrigerant charge port of this product have electric expansion valve.
The valve will be closed at end of refrigerant charging. However the valve 
will be opened on operation after refrigerant charging (check operation, 
nomal operation, etc.).
If the tank is left with the valve open, the amount of refrigerant which is 
properly charged may be off the point.

Make sure to perform the check operation after installation. Other-
wise, the malfunction code “U3” will be displayed and normal opera-
tion cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal 
operation. Performance may drop due to the failure of “Judgment of 
piping length”.

Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.

The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is 
completed. (See chapter 13)

The check operation cannot be performed in recovery or other ser-
vice modes.

11-2-1 Procedure of Adding Refrigerant charging
1.

Make sure the following works are complete in accordance with the 
installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Installation work for indoor unit

2.

Calculate the “additional charging amount” using “How to calculate the 
additional refrigerant to be charged” in 

“6-5 Example of connection”

.

3.

Open the valve B (

See the figure 30

. The valve A,C and the liquid 

pipe, gas pipe, equalizer pipe shutoff valves must be left closed), and 
charge the refrigerant of the “additional charging amount” from the 
liquid side shutout valve service port.

(Refer to figure 30)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

High side equalizer pipe shutoff valve

5.

Gas pipe shutoff valve

6.

Low side equalizer pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Refrigerant charge port

9.

Valve A

10.

Valve B

11.

Valve C

12.

Outside unit A

13.

Outside unit B

14.

Indoor unit

15.

Field pipings

16.

Refrigerant flow

17.

Shutoff valve

18.

Service port

4.

If the “additional charging amount” was charged fully, close the valve 
B and go to step 6.
If the “additional charging amount” was not charged fully, close the 
valve B and go to step 5.

5.

Perform the refrigerant charging following [Automatic refrigerant 
charging operation procedure] as shown below. And charge the 
remaining refrigerant of the “additional charging amount”.

NOTE

For performing the automatic refrigerant charging operation, the push 
button on the PC-bord (A1) of outside unit are used. (See figure 29.)
And the refrigerant are charged from the refrigerant charge port via 
the valve A. (See figure 31.) For operating the push button and open-
ing or closing the valves, follow the procedure.

During Automatic refrigerant charging operation, the system will 
select charging mode (cooling mode or heating mode) by the tem-
perature condition as follows.

When charging in cooling mode, the system will stop operation when 
the required amount of refrigerant is charged.
During charging in heating mode, a person must manually close 
valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to 
charge based on the “additional charging amount” in step 2 and the 
charged amount in step 3.

The refrigerant will be charged about 66 lb in one  hour at outdoor 
temp. 86°F DB (about 26 lb at outdoor temp. 32°F DB).

During Automatic refrigerant charging operation, you can stop the 
operation forcedly by pushing MODE button (BS1).

(Refer to figure 31)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

High side equalizer pipe shutoff valve

5.

Gas pipe shutoff valve

6.

Low side equalizer pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Refrigerant charge port

9.

Valve A

10.

Valve B

11.

Valve C

12.

Outside unit A

13.

Outside unit B

14.

Indoor unit

15.

Field pipings

16.

Refrigerant flow when charging

17.

Shutoff valve

18.

Service port

19.

The refrigerant will be charged about 66 lb in one hour at out-
door temp. 86°FDB (26 lb at 32°FDB). (According to outdoor 
temp. or the refrigerant amount in the tank, the charging rate 
may speed up). If you need to speed up in case of multi sys-
tem, connect the refrigerant tanks to each outside unit.

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

Outdoor temp. : 32˚F DB ~  109˚F DB
Indoor temp. :

50˚F DB ~  90˚F DB

Less than above range

Cooling mode

Heating mode

Содержание RXYQ72PAYD

Страница 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Страница 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Страница 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Страница 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Страница 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Страница 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Страница 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Страница 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Страница 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Страница 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Страница 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Страница 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Страница 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Страница 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Страница 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Страница 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Страница 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Страница 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Страница 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Страница 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Страница 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Страница 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Страница 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Страница 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Страница 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Отзывы: