5 Installation
Installation and operation manual
24
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV system air conditioner
4P370473-1C – 2016.07
Screw size
Tightening torque (N•m)
M3.5 (A1P)
0.80~0.96
In case of single outdoor unit installation
F
1
F
2
F
1
F
2
Q
1
Q
2
F1
F1
F2
F2 Q1 Q2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
F1 F2
b
c
a
d
e
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
A1P
a
Outdoor unit PCB (A1P)
b
Use the conductor of sheathed wire (2 wire) (no polarity)
c
Terminal board (field supply)
d
Indoor unit
e
Outdoor unit
In case of multi outdoor unit installation
F1 F2 F1 F2 Q1 Q2
Q1 Q2
A1P
d
d
e
f
b
a
c
Q1 Q2
a
Unit A (master outdoor unit)
b
Unit B (slave outdoor unit)
c
Unit C (slave outdoor unit)
d
Master/slave transmission (Q1/Q2)
e
Outdoor/indoor transmission (F1/F2)
f
Outdoor unit/other system transmission (F1/F2)
▪ The interconnecting wiring between the outdoor units in the same
piping system must be connected to the Q1/Q2 (Out Multi)
terminals. Connecting the wires to the F1/F2 terminals results in
system malfunction.
▪ The wiring for the other systems must be connected to the F1/F2
(Out-Out) terminals of the PCB in the outdoor unit to which the
interconnecting wiring for the indoor units is connected.
▪ The base unit is the outdoor unit to which the interconnecting
wiring for the indoor units is connected.
5.7.5
To finish the transmission wiring
After installing the transmission wires inside the unit, wrap them
along with the on-site refrigerant pipes using finishing tape, as
shown in figure below.
a
b
c
d
e
a
Liquid pipe
b
Gas pipe
c
Insulator
d
Transmission wiring (F1/F2)
e
Finishing tape
5.7.6
To route and fix the power supply
NOTICE
When routing earth wires, secure clearance of 25 mm or
more away from compressor lead wires. Failure to observe
this instruction properly may adversely affect correct
operation of other units connected to the same earth.
The power supply wiring can be routed from the front and left side.
Fix it to the lower mounting hole.
d
c
X1M
a
b
d
a
c
d
X1M
b
8~12 HP
14~20 HP
A
A
A
d
d
a
Power supply (possibility 1)
(a)
b
Power supply (possibility 2)
(a)
c
Power supply (possibility 3)
(a)
. Use conduit.
d
Tie wrap
(a)
Knockout hole has to be removed. Close the hole to avoid
small animals or dirt from entering.
5.7.7
To connect the power supply
The power supply must be clamped to the plastic bracket using field
supplied clamp material.
The green and yellow striped wire must be used for earthing only