15
English
B.
Where there is a room division but there is an opening
between the rooms sufficiently large to permit a free flow of air
back and forth.
(Where there is an opening without a door or where there are open-
ings above and below the door which are each equivalent in size to
0.15% or more of the floor area.)
3.
Calculating the refrigerant density using the results of the calcula-
tions in steps 1 and 2 above.
If the result of the above calculation exceeds the maximum concen-
tration level then make similar calculations for the second then third
smallest room and so until the result falls short of the maximum con-
centration.
4.
Dealing with the situations where the result exceeds the maximum
concentration level.
Where the installation of a facility results in a concentration in excess
of the maximum concentration level then it will be necessary to
revise the system.
Please consult your Daikin supplier.
NOTES
total volume of refrigerant in the
refrigerant system
≤
maximum concen-
tration level (lb./ft
3
)
size (ft
3
) of smallest room in which
there is an indoor unit installed
Opening between rooms