• Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
1
1
• VRV Systems • Outdoor Units
3
1
Specifications
Safety devices
PC board fuse
HPS
HPS
HPS
HPS
HPS
Inverter overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
Fan motor driver
overload
protector
HPS
Over current
relay
Over current
relay
Over current
relay
Over current
relay
Over current
relay
Fan motor driver
overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Inverter overload
protector
Over current
relay
PC board fuse
PC board fuse
PC board fuse
PC board fuse
PC board fuse
Standard
Accessories
Standard Accessories
Installation manual
Quantity
1
1
1
1
1
1
Standard Accessories
Operation manual
Quantity
1
1
1
1
1
1
Standard Accessories
Connection pipes
Quantity
4
4
4
4
4
4
Notes
Nominal cooling capacities are based on : indoor temperature : 27×CDB, 19×CWB, outdoor temperature : 35×CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20×CDB, outdoor temperature : 7×CDB, 6×CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound pressure
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound level of a
multi system is
determined by
the individual
outdoor unit and
installation
condition
Sound values
The refrigerant
charge of the
system must be
less than 100 kg.
This means that
in case the
calculated
refrigerant
charge is equal to
or more than 95
kg, you must
divide your
multiple outdoor
system into
smaller
independent
systems, each
containing less th
Sound values are measured in a semi-anechoic room.
1-2 TECHNICAL SPECIFICATIONS
RXYHQ26P8W1B
RXYHQ28P8W1B
RXYHQ30P8W1B
RXYHQ32P8W1B
RXYHQ34P8W1B
RXYHQ36P8W1B
Capacity
Cooling
kW
71.40
77.00
82.50
89.00
94.00
98.00
Heating
kW
81.50
88.00
94.00
102.00
107.00
113.00
COP
Cooling
4.09
4.12
3.96
3.99
3.85
3.89
Heating
4.34
4.44
4.31
4.40
4.29
4.37
Capacity range
HP
26
28
30
32
34
36
Power input
(nominal)(50Hz
)
Cooling
kW
17.46
18.69
20.83
22.31
24.42
25.19
Heating
kW
18.78
19.82
21.81
23.18
24.94
25.86
PED category
Category II
Max n× of indoor units to be connected
42
45
48
52
55
58
Indoor index
connection
Minimum
325
350
375
400
425
450
Maximum
845
910
975
1,040
1,105
1,170
Casing
Colour
Daikin White
Material
Painted galvanised steel
1-2 TECHNICAL SPECIFICATIONS
RXYHQ12P8W1B
RXYHQ16P8W1B
RXYHQ18P8W1B
RXYHQ20P8W1B
RXYHQ22P8W1B
RXYHQ24P8W1B