SiUS331708EA
Troubleshooting by Error Code
Service Diagnosis
152
4. Troubleshooting by Error Code
4.1
Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error code
Operation
lamp
Description
Reference
Page
Indoor Unit
A0
l
External protection device abnormality
A1
l
Indoor unit PCB abnormality
A3
l
Drain level control system abnormality
A6
l
Fan motor lock, overload
Indoor fan motor abnormality
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
A7 (
∗
1)
k
Swing flap motor abnormality
A8
l
Power supply voltage abnormality
Blower motor stops for over/under voltage
A9
l
Electronic expansion valve coil abnormality, dust clogging
AA
l
Gas furnace abnormality
AF (
∗
1)
k
Drain level above limit
AJ
l
Capacity determination device abnormality
C1
l
Transmission abnormality between indoor unit PCB and fan PCB
Blower motor communication error
Climate Talk communication error
C4
l
Heat exchanger liquid pipe thermistor abnormality
C5
l
Heat exchanger gas pipe thermistor abnormality
C6
l
Combination error between indoor unit PCB and fan PCB
Blower motor HP mismatch
Indoor blower does not have required parameters to function
C9
(
∗
2)
l
Suction air thermistor abnormality
Remote sensor abnormality
CA
l
Discharge air thermistor abnormality
CC
k
Humidity sensor system abnormality
CE (
∗
1)
k
Infrared presence/floor sensor error
CJ
(
∗
2)
k
Remote controller thermistor abnormality
Outdoor Unit
E1
l
Outdoor main PCB abnormality
E3
l
Activation of high pressure switch
E4
l
Activation of low pressure sensor
E5
l
Inverter compressor motor lock
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
H9
l
Outdoor air thermistor abnormality
J3
l
Discharge pipe thermistor abnormality
J5
l
Suction pipe thermistor abnormality
J6
l
Outdoor heat exchanger deicer thermistor abnormality
J7
l
Outdoor heat exchanger liquid pipe thermistor abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
PCB (for inverter compressor) abnormality
L4
l
Radiation fin temperature rise abnormality
Содержание RXSQ24TAVJU
Страница 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Страница 289: ...SiUS331708EA Wiring Diagrams Appendix 276 1 Wiring Diagrams 1 1 Outdoor Unit RXSQ24 36TAVJU 3D109545A...
Страница 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Страница 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Страница 292: ...Wiring Diagrams SiUS331708EA 279 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 293: ...SiUS331708EA Wiring Diagrams Appendix 280 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Страница 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Страница 308: ...Wiring Diagrams SiUS331708EA 295 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...