4 Unit installation

Installation manual

6

RXQ-A_ARXQ-A

R32 split series

3P664524-2A – 2021.07

4

Unit installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

4.1

Preparing the installation site

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

4.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

>150

>50

>300

(mm)

b

a

>100

>50

>150

>50

b

b

a

>100

b

a

a

b

a

>100

a

Air outlet

b

Air inlet

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

The  outdoor  unit  is  designed  for  outdoor  installation  only,  and  for
ambient  temperatures  within  the  following  ranges  (unless  otherwise
specified in the operation manual of the connected indoor unit):

Cooling mode

Heating mode

10~46°C DB

–15~24°C DB

4.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

It  is  recommended  to  provide  at  least  150  mm  of  free  space  below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See 

"4.2 Mounting

the outdoor unit"

 [

4

 6] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

Содержание RXQ25AMV1B

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXQ25AMV1B RXQ35AMV1B ARXQ25AMV1B ARXQ35AMV1B...

Страница 2: ...jem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodyt...

Страница 3: ...ation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe an...

Страница 4: ...the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Charging refrigerant see 6 Charging refrigerant 48 WARNI...

Страница 5: ...ALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT ONLY the outdoor unit but the connected indoor unit will operate as well Worki...

Страница 6: ...und reflections INFORMATION The sound pressure level is less than 70 dBA The outdoor unit is designed for outdoor installation only and for ambient temperatures within the following ranges unless othe...

Страница 7: ...ping material Piping material Phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping temper grade and thickness Outer diameter Temper grade Thickness t a 6 4 mm...

Страница 8: ...5 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate NOTICE ALWAYS use a recommended bubble test solution from your wholesaler NEVER use...

Страница 9: ...nt 6 4 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential G...

Страница 10: ...e at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the termina...

Страница 11: ...nt leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are ful...

Страница 12: ...verview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circui...

Страница 13: ...witch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Tran...

Страница 14: ......

Страница 15: ......

Страница 16: ...3P664524 2A 2021 07 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: