Normal Operation
Part 4 Functions and Control
83
5. Normal Operation
5.1 List of Functions in Normal Operation
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
: equipped
—: not equipped
5.2 Compressor Control
In order to provide a steady capacity, the compressor capacity is controlled to achieve
temperature Te during cooling operation.
During cooling operation
The compressor capacity is controlled so Te approaches TeS (target value of temperature).
1. VRTsmart Control
When all the connected indoor units are VRTsmart control applicable models
Applicable models: FXFSQ-AR, FXMQ-PB
The required capacity is calculated based on the operation condition of each individual indoor
unit and this data is transmitted to the outdoor unit. The outdoor unit adjusts the refrigerant
temperature of the whole system to an adequate value according to the indoor unit that needs
the most capacity.
In case of target evaporation temperature adjustment, first the capacity is adjusted by changing
the indoor unit airflow to L tap. If the capacity is still too much, the target evaporation
temperature is elevated further to adjust.
2. VRT Control
When one or more of the connected indoor units are not VRTsmart control applicable
models
If the required capacity becomes low in all indoor units (Room temperature Th1 – set
temperature), the target evaporation temperature is elevated further to adjust. In the outdoor
unit, the difference of temperature (∆T) in all indoor units is checked and the set temperature is
changed. Unlike VRTsmart control, there is no airflow control of the indoor units.
3. Te fix Control
The target evaporation temperature is not changed.
Te value (Set in mode 2-8)
Te: Low pressure equivalent saturation temperature (°C)
TeS: Te target value (varies according to Te setting, compressor operation frequency, etc.)
Part Name
Electric
Symbol
RXQ6-12A
RXQ14A
RXQ16-20A
Function of Functional Part
Inverter compressor 1
M1C
PI control by Te target.
Inverter compressor 2
M2C
—
—
Inverter fan 1
M1F
Fan speed 10 steps to keep
minimum Tc target 34°C.
Inverter fan 2
M2F
—
Electronic expansion valve
(Injection)
Y2E
0-480 pulse at compressor on
Electronic expansion valve
(Refrigerant auto charge)
Y4E
Minimum pulse
Solenoid valve (Oil return 1)
Y3S
Only close if Pc – Pe < 0.3 MPa
(when compressor off)
Solenoid valve (Oil return 2)
Y4S
—
—
Standard (Factory
setting)
High
6
7
8
9
10
11
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...