Outline of Control (Indoor Unit)
SiAF341904E
98
Part 4 Functions and Control
8.7 Drain Pump Control
8.7.1 Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
The aim of residual operation after thermostat OFF is to eliminate the dew that condenses
on the indoor heat exchanger during cooling operation.
8.7.2 If the Float Switch is OFF with the Thermostat ON in Cooling
Operation
When the float switch turns OFF, the thermostat turns OFF simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
1: If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
2: If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code
A3
is displayed on the remote controller.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
3: After
A3
is displayed and the unit comes to an abnormal stop, the thermostat will remain
OFF even if the float switch turns ON again.
Float s
w
itch
Error display
Thermostat
(r
u
nning)
OFF
OFF
O
N
O
N
O
N
OFF
Drain p
u
mp
O
N
OFF
5 min.
OFF
OFF
O
N
O
N
O
N
OFF
O
N
OFF
5 min.
5 min. 5 sec.
5 sec.
Float s
w
itch
Error display
Thermostat
(r
u
nning)
Drain p
u
mp
A3
∗
1
∗
3
∗
2
Содержание RXQ12AHR
Страница 267: ...SiAF341904E Troubleshooting by Error Code Part 6 Service Diagnosis 261 Reference CHECK 7 Refer to page 293...
Страница 312: ...SiAF341904E 306 Part 7 Appendix 1 Wiring Diagrams 307 1 1 Outdoor Unit 307 1 2 VRV Indoor Unit 310 Part 7 Appendix...
Страница 313: ...SiAF341904E Wiring Diagrams Part 7 Appendix 307 1 Wiring Diagrams 1 1 Outdoor Unit RXQ6 8 10 12ARY1 3D112175E...
Страница 314: ...Wiring Diagrams SiAF341904E 308 Part 7 Appendix RXQ14ARY1 2D112174G...
Страница 315: ...SiAF341904E Wiring Diagrams Part 7 Appendix 309 RXQ16 18 20ARY1 2D112524F...
Страница 317: ...SiAF341904E Wiring Diagrams Part 7 Appendix 311 1 2 2 Auto Grille Panel BYCQ125EASF for FXFSQ 3D108035...
Страница 319: ...SiAF341904E Wiring Diagrams Part 7 Appendix 313 FXMQ40 50 63 80 100ARV1 3D112427A...
Страница 320: ...Wiring Diagrams SiAF341904E 314 Part 7 Appendix 1 2 4 Wall Mounted Type FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...