7
|
Piping installation
Installer reference guide
43
R32 split series
4P751614-2 – 2023.09
WARNING
▪
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
▪
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
▪
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
▪
Do NOT pierce or burn refrigerant cycle parts.
▪
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
▪
Be aware that the refrigerant inside the system is odourless.
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg]/1000
Contact your installer for more information.
7.4.3 Precautions when charging refrigerant
7.4.4 To determine the additional refrigerant amount
If the total liquid piping
length is…
Then…
≤10 m
Do NOT add additional refrigerant.
>10 m
R=(total length (m) of liquid piping–10 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
INFORMATION
Piping length is the one-way length of liquid piping.
7.4.5 To determine the complete recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.