Installation Guidelines 

Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet air

fl

 ow, follow the installation guidelines below.

• 

For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

• 

More than 

3-15/16 (100)

More than 

13-3/4 (350)

Side view

47-1/4

(1200)

or less

More than 

1-15/16 (50)

More than 

1-15/16 (50)

More than 

13-3/4 (350)

Top view

More than 

3-15/16 (100)

Top view

unit: inch (mm)

More than 3-15/16 (100)

More than 13-3/4 (350)

More than 

1-15/16 (50)

Wall facing one side

Walls facing two sides

Walls facing three sides

Precautions on Installation

Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.

• 

In accordance with the foundation drawing, 

fi

 x the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 

• 

foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 3/4 inch (20mm) from the foundation surface.

• 

3/4 inch 

(20mm)

Outdoor Unit Installation

Installing outdoor unit

1. 

When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”.

1) 

If drain work is necessary, follow the procedures below.

2) 

2. 

Drain work (Heat pump models)

Use drain plug for drainage.

1) 

If the drain port is covered by a mounting base or 

fl

 oor surface, place 

2) 

additional foot bases of at least 1-1/4 inch (30mm) in height under the outdoor 
unit’s feet.
In cold areas, do not use a drain hose with the outdoor unit. 

3) 

(Otherwise, drain water may freeze, impairing heating performance.)

Drain port

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 5/8 inch (16mm))

01_EN_3P273470-2.indd   5

01_EN_3P273470-2.indd   5

1/6/2011   12:04:44 PM

1/6/2011   12:04:44 PM

Содержание RXN15KEVJU

Страница 1: ...nstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXN15KEVJU RKN15KEVJU RXN18KEVJU RKN18KEVJU RXN24KEVJU RKN24KEVJU 00_CV_3P273470 2 i...

Страница 2: ...not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting i...

Страница 3: ...nd fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open flames If the gas l...

Страница 4: ...10ft 3m away depending on radio wave conditions In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 8 Since drain flows out of t...

Страница 5: ...height Min allowable length Max allowable length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required for refr...

Страница 6: ...urely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their leng...

Страница 7: ...damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N m Valve cap tightening...

Страница 8: ...1MPa 1 3 Close gauge manifold s low pressure valve Lo and stop vacuum pump 4 Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 Remove caps...

Страница 9: ...ending Selection of copper and heat insulation materials 7 2 When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam 1 Heat transfer rate 0 041 to 0...

Страница 10: ...operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller Press MODE button and select the cooling mode 1 Press ON OFF button to turn on the system 2 Press both o...

Страница 11: ...o tighten the screws Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection plate by removing the 2 screws and d...

Страница 12: ...start back up once the temperature rises again Remove the 3 screws on the side and remove the top plate of the outdoor unit 1 Remove the drip proof cover 2 Cut the jumper J6 of the PCB inside 3 J5 J7...

Страница 13: ...ion in accordance with the operation manual to ensure that all functions and parts 1 3 such as fin movement are working properly The air conditioner requires a small amount of power in its standby mod...

Страница 14: ...3P273470 2 M10B141 1102 HT Two dimensional bar code is a code for manufacturing 00_CV_3P273470 2 indd 2 00_CV_3P273470 2 indd 2 12 15 2010 2 29 23 PM 12 15 2010 2 29 23 PM...

Отзывы: