Installation Space Requirements
• Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation space
requirements below.
•
For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.
More than
1-15/16 (50)
More than
1-15/16 (50)
More than
5-7/8 (150)
More than
3-15/16 (100)
More than
1-15/16 (50)
More than
3-15/16 (100)
Side view
47-1/4
(1200)
or less
Wall facing one side
Walls facing two sides
Top view
Top view
More than 5-7/8 (150)
More than
11-13/16 (300)
More than
1-15/16 (50)
Walls facing three sides
unit: inch (mm)
unit: inch (mm)
Top view
More than 3-15/16 (100)
More than
13-3/4 (350)
More than
1-15/16 (50)
Walls facing three sides
More than
3-15/16 (100)
More than
13-3/4 (350)
Side view
47-1/4
(1200)
or less
Wall facing one side
More than
1-15/16 (50)
More than
1-15/16 (50)
Top view
More than
3-15/16 (100)
Walls facing two sides
More than
13-3/4 (350)
09/12 class
15/18/24 class
Outdoor Unit Installation
1.
Installing the outdoor unit
1) When installing the outdoor unit, refer to “
Precautions for Selecting a Location
” and the “
Outdoor Unit Installation Diagram
”.
2) If drain work is necessary, follow the procedures on the next page.