The RTD-10 can be configured to operate in a duty/standby configuration 
suitable for IT and Telecoms applications. An RTD-10 master together with up 
to 7 RTD-10 slaves can be configured to operate in a rotating duty/standby 
configuration with the following features:

Up to 8 duty/standby groups

All units run on fault

1 or 2 standby units

Daily, Weekly or Multi-week duty rotation

Two level alarm on high temperature and unit fault

Thermistor space temperature alarm

A7 (Louvre) fault code filtering

DUTY/STANDBY OPERATION

Under 'no fault' conditions the system will operate with 1 or 2 units in standby 
and the remaining units operational (2 unit standby is only available if there are 
at least thee RTD groups). Default rotation time is 7 days, input S3 can be 
configured to select rotation times of 1 day, 2 weeks or 4 weeks if required 
using specific resistor values. In addition a test-mode is available by placing a 
0 ohm link on S3 which will cause the system to operate in test mode with a 60 
second rotation time. The system should only be operated in test mode for 
short time periods.

The RTD-10 with Address 0 (SW1.5 to SW1.8 OFF) is the Duty/Standby 
master. All inputs and outputs are wired to the Master. Slave inputs should not 
be wired. Slave output relays indicate the Alarm Level for that slave only.

A/C UNIT OPERATION

The unit mode is set to COOL and the mode button on the Master remote 
controller is locked to prevent change. The on/off button is also locked. The 
setpoint and fanspeed can be set from the RTD-10 master or the remote 
controller on the master group. If S1 and S2 are wired then setpoint and 
fanspeed are set by the RTD-10 inputs and the corresponding buttons on the 
remote controller are locked. If S1 and S2 are not wired then the buttons on the 
master remote controller are unlocked and can be used to set operating 
values. In this mode the setpoint is 

limited

 to the range 20 to 32°C.

Duty/Standby Operation

ALARM OPERATION

Relay outputs R1 and R2 on the Master RTD-10 operate respectively as Level 
1 and Level 2 alarm outputs. If a Level 2 alarm occurs then both R1 

and

 R2 will 

be closed. All units will run if a Level 1 or Level 2 alarm occurs.

All unit return air temperatures are monitored and alarm levels 1 and 2 are set 
respectively at 2°C and 4°C above operating setpoint. The Auxiliary Space 
Temperature sensor has the same alarm limits applied. 

Any unit fault other than code A7 will result in a Level 2 alarm being generated. 
An A7 (louvre fault) will generate a Level 1 alarm, but will not force units on.

The RTD-10 master will monitor all of the RTD slave devices discovered after 
power-up. If any of the RTD slave devices fail to respond the RTD-10 will raise 
a Level 2 alarm after 1 to 2 minutes. 

Alarm

Reasons

Alarm Level 1
Output R1

Unit Return Air > Se 2°C
Aux. Space Temperature > Se 2°C 
A/C Unit Louvre Fault (A7)
Alarm Level 2 Exists

Alarm Level 2
Output R2

Unit Return Air > Se 4°C
Aux. Space Temperature > Se 4°C
A/C Unit Fault (except A7)
A/C Unit Missing (U5 Fault)
RTD-10 Slave Missing (master RTD-10)
RTD-10 No slaves found (master RTD-10)
RTD-10 Master not found (slave RTD-10)

If a Level 1 or Level 2 alarm occurs due to a unit or communications fault then 
all units will run until all faults are cleared. 

If a Level 1 or Level 2 alarm occurs due to a high temperature on an indoor unit 
or the Auxiliary Space sensor then all units will run until temperature has reset 
and will continue to run on for 20 minutes before reverting to normal 
Run/Standby operation. In Test Mode (rotation = 60s) the run on time will be 40 
seconds..

If a Level 2 alarm occurs due to an Indoor Unit Fault then all units will run until 
the Indoor Unit Fault has cleared and will continue to run on for 10 minutes 
before reverting to normal Run/Standby operation. In Test Mode (rotation = 
60s) the run on time will be 20 seconds.

OVERRIDE ALL ON/OFF

Input S5 is a volt-free contact input that overrides all units ON if closed circuit. 
Input S6 is a volt-free contact input which overrides all units OFF if closed 
circuit.

AUXILLIARY SPACE SENSOR

An auxiliary space sensor is required to provide alarm monitoring in the 
controlled space. 

The sensor should be a 10kΏ NTC Thermistor mounted on a suitable vertical 
surface in the monitored space.  The sensor should be wired to the RTD-10 
using a twisted pair cable no longer than 100 metres. The Auxiliary sensor will 
raise alarms even if the units are overridden off.

Duty/Standby Operation

INSTALLATION

All RTD interfaces must be networked together using the 3 wire  RS485 
network, each RTD must then have a network address set in the range 0 to 7 
(see section 

RTD Networking

). The RTD-10 Duty/Standby Master must have 

an address of 0. The remaining RTD slaves should have addresses in the 
range 1 to 7. If there are less than 7 slaves then start the addressing at 1 and 
allocate each slave consecutively upwards.

The Master and Slave RTD-10s will both initially indicate a Level 2 alarm. The 
master alarm will clear when it discovers at least one slave RTD-10. The slave 
alarm will clear when the master  discovers the slave. If communications fails 
with a slave RTD-10 the master will generate a  Level 2 alarm after 120s.

CONFIGURATION

The Run/Standby configuration is selected using the RTD-10 DIP switch 
settings. Both master and slave devices must have the DIP switches set. The 
position of SW1.4 on the master determines whether the system operates with 
1 unit or 2 unit standby. The possible switch configurations are as follows:

1 Unit Standby

2 Unit Standby

5 6 7 8

ON

1 2 3 4

5 6 7 8

ON

1 2 3 4

INPUT CONFIGURATION

Input

Name

Range (default)

S1

Setpoint

0..10kΏ : 16..32°C (

from RC

)

S2

Fanspeed

Low=1.1kΏ, High=2.2kΏ, HighHigh*=3.3kΏ (

from RC

)

S3

Rotation

60s<=1.1kΏ,  1 Day=2.2kΏ, 

1 Week

=3.3kΏ,

 

2 Weeks=4.7kΏ, 

4 Weeks=6.8kΏ

S4

Auxiliary
Space 
Temp

10kΏ NTC Thermistor 

Recommended part:  RS Stock No. 813-806

S5

All On

All On = Closed Circuit, 

Normal Operation 

= Open Circuit

S6

All Off

All Off = Closed Circuit, 

Normal Operation 

= Open Circuit

*HighHigh fanspeed operates if available, otherwise selects High fanspeed

RELAY CONFIGURATION

Output

Name

Operation

R1

Alarm 
Level 1

Closed when Alarm Level 1 or 2 occurs

R2

Alarm 
Level 2

Closed when Alarm Level 2 occurs

Caution

: Relays rated for maximum 1A, 24VAC/30VDC

MODBUS OPERATION

When operating in Duty/Standby mode the RTD devices CANNOT be 
connected to an external Modbus Master as this will disrupt operation.

 Duty/Standby Operation

7 Day Rotation

RUN

RUN

STANDBY

RTD-10

RTD-10

RTD-10

P1,P2

P1,P2

P1,P2

RS485

Upto 8 Groups

Содержание RTD-10

Страница 1: ...ikin VRV and Skyair ranges of air conditioners and VAM and VKM ventilation units The interface is compatible with all units that have a P1 P2 remote controller network connection and allows control of up to 16 units in a single group Control Functions HARDWIRED CONTROL Unit control can be achieved through resistance inputs using resistor potentiometer and volt free contact inputs BMS INTEGRATION U...

Страница 2: ...terlock Master Cooling System Inhibit 5 6 7 8 ON 1 2 3 4 R1 Mode Interlock Relay Closed Unit ON No Fault Mode Auto Heat or Heat INTERLOCK SLAVE MODE To operate in slave mode the input S4 operates as a Volt free inhibit input When the inhibit signal is closed circuit the RTD 10 will prevent the A C unit from operating Input S4 operation can be inverted by inserting a Short Circuit on input S2 The R...

Страница 3: ...larm occurs due to a unit or communications fault then all units will run until all faults are cleared If a Level 1 or Level 2 alarm occurs due to a high temperature on an indoor unit or the Auxiliary Space sensor then all units will run until temperature has reset and will continue to run on for 20 minutes before reverting to normal Run Standby operation In Test Mode rotation 60s the run on time ...

Страница 4: ... written to the A C on every register write On Change updates are only sent if the value written changes Central locks the corresponding RC button Local unlocks the RC button and prevents any updates from the RTD MONITORING Unit data is available for each of the indoor units on the P1 P2 network All readback data is available in analogue Input Registers Input registers are numbered using the indoo...

Отзывы: