Maintenance
EN
22
FA Daikin/ROTEX PG - 05/2017
008.15 442 44_01 - EN
8
Maintenance
8.1
Maintenance intervals
8.2
Maintenance activities
8.2.1
Replacing a defective circulation pump
1. Close the red thermometer ball valve and the ball valve in the pump line
(90° setting).
2. Replace the circulation pump (see instructions of the manufacturer of
the pump).
3. Open the thermometer ball valve and the ball valve (0° setting).
When
Activity
Monthly
Perform a visual inspection of the heating system
and verify tightness.
If required
Replace the circulation pump.
DANGER
ELECTRIC SHOCK CAUSED BY LIVE PARTS
•
Disconnect the mains voltage supply before performing the work and ensure
that it cannot be switched on.
Failure to follow these instructions will result in death or serious injury.