![Daikin Rotex A1 BO Series Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/daikin/rotex-a1-bo-series/rotex-a1-bo-series_installation-and-maintenance-instructions-manual_3404037036.webp)
36
FA ROTEX A1 BOe - 02/2014
7
x
Oil burner
7.
Rotate burner by 180° around the motor axis and put aside on
the burner flange.
8.
Hang in the burner through the opening in the holder plate in
the service screw and engage in the bayonet lock. Tighten the
service screw.
Î
The burner is now in service position.
Installation is carried out in reverse order.
7.4.2 Removing/fitting the flame tube
The flame tube can be removed with mounted burner and open
boiler.
1.
Switch off main heater switch.
2.
Remove the noise damping hood and boiler cladding (see
section 9.2.1).
3.
Open the combustion chamber (see chapter 9.2.5).
4.
Rotate flame tube (turn bayonet lock counter clockwise by 1/8
rotation).
Install the flame tube in reverse sequence.
7.4.3 Removing/fitting the burner
1.
Switch off main heater switch.
2.
Remove the noise damping hood and boiler cladding (see
section 9.2.1).
3.
Unscrew the oil hoses from the oil filter.
4.
Only on A1 BO 35-e:
Removing the flame tube (see section 7.4.2).
5.
Removing burner from burner flange (see section 7.4.1,
working steps 3 - 6).
6.
Unscrew four fixing screws from the burner flange.
7.
Lift burner flange with recirculation tube and flame tube out of
the burner chamber.
Install the burner in reverse sequence.
8.
Start burner, check function and settings (see section 7.3).
7.5 Removing/fitting the air nozzle
For certain output ranges, air nozzles that differ from the series
condition must be fitted in the mixer device of the burner. The ap-
propriate air nozzle is supplied with the changeover kit URS
(see tab. 7-1).
Tools required: Allen key SW 3.0 mm
1.
Bring burner in service position (see section 7.4.1).
2.
Unscrew the fixing screws (3 in number) on the air nozzle.
3.
Remove the air nozzle from the mixer device.
Installation of the air nozzle is carried out in reverse order.
4.
Adjust the distance of the oil-air nozzle to dimension "Y" in
accordance with tab. 7-1 (see section 7.3.6).
Fig. 7-12 Service position
WARNING!
Danger of burning - hot surfaces (flame tube).
Ɣ
Let the burner cool down sufficiently before
removing the flame tube.
Ɣ
Wear protective gloves.
1
Air nozzle
2
Fastening bolts
Fig. 7-13 Air nozzle in mixer device
On the burner BLB 34e the entire mixer device must be
replaced for output adapting.