Unit Options
www.DaikinApplied.com 93
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Check belt tension two times during the first 24 hours of
operation and periodically thereafter. To adjust belt tension,
simply loosen four fasteners (two on each side of the motor
plate) and slide the motor plate away from the fan shaft until
proper belt tension is attained. On some fans, fasteners
attaching the motor to the motor plate must be loosened to
adjust the belt.
It is very important that the drive pulleys remain in proper
alignment after adjustments are made (see
).
Misalignment of pulleys results in premature belt wear noise,
vibration, and power loss.
Fasteners and Setscrews
Any fan vibration has a tendency to loosen mechanical
fasteners. A periodic inspection should include checking all
fasteners and set screws for tightness. Particular attention
should be paid to setscrews attaching the propeller to the shaft
and the shaft to the bearings. Loose bearing set screws will
lead to premature failure of the fan shaft.
Figure 110: Drive Pulley Alignment
Exhaust Fan ON/OFF Control
The exhaust fans are turned on and off based on building
static pressure, outdoor air damper position, and discharge
fan capacity. Exhaust fans do not have to always run while the
supply fan is on, as does a return fan. They are turned on and
off through output MCB-B02 on the Main Control Board. For
detailed information on Propeller Exhaust Fan Control, refer to
the operation manual supplied with the unit (
).
Exhaust Fan Troubleshooting
provides guidelines for troubleshooting problems with
the propeller exhaust fan options. A list of parts is provided in
.
Figure 111: Propeller Exhaust Fan Replacement Parts List
Table 22: Propeller Exhaust Fan Troubleshooting
Problem
Cause
Corrective Action
Reduced Airflow
System resistance is too high
Check backdraft dampers for proper operation. Remove obstructions in ductwork. Clean dirty filters. Check for
adequate supply for air exhaust fans or exhaust air for supply fans
Unit running backwards
See “Prestarting Checks” on page 94
Fan speed too low
Increase fan speed
Excessive dirt on propeller
Clean propeller
Excessive Noise
Bearings
Tighten bearing collars and setscrews. Lubricate bearings. Replace defective bearings
V-Belt drive
Tighten pulleys on motor shaft and fan shaft. Adjust belt tension. Align pulleys. Replace worn belts or pulleys
Excessive vibration
Clean dirt build-up from propeller. Check all setscrews and fasteners for tightness. Check for worn bearing.
Correct propeller imbalance. Check for loose dampers, guards or ductwork
Defective motor
Replace motor