Electrical Installation
www.DaikinApplied.com 53
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Field Control Wiring
DANGER
Electrical shock hazard. Can cause severe injury or death.
Connect only low voltage NEC Class II circuits to terminal
block TB5.
Reinstall and secure all protective deadfront panels when the
wiring installation is complete.
Roof Pak applied rooftop units are available with several
control arrangements which may require low voltage field
wiring. Detailed descriptions of various field control wiring
options and requirements are included in the “Field Wiring”
, “MicroTech III Applied Rooftop Unit
Controller.” Refer to the unit wiring diagrams for additional
installation information.
Wiring must comply with applicable codes and ordinances.
The warranty is voided if wiring is not in accordance with these
specifications.
RPS, RDT, and RFS Units
All field control wiring connections are made at the class II
terminal block TB2, which is located in the main control panel.
Field wiring connections to the 115-volt receptacle and lights
are made at terminal block TB7, which is also located in the
. Two 7/8" knockouts are provided for wire entry.
Figure 72: RDT, RFS, RPS Field Control WiringConnections
RFS/RCS Units
The RCS unit receives 115-volt and 240-volt control circuit
power and a number of control signals from the RFS unit.
Two 7/8" knockouts are provided in the right side of the RCS
control box.
Interconnecting wiring enters the RFS unit through 7/8"
knockouts in the bottom of the main control panel. The
interconnecting wiring is connected to TB4 in the RFS unit and
. A 7/8" knockout is also
available in the end of the unit base as shown in
NOTE:
If a single conduit containing 24V and 115V wiring is
run above the roof line between the RFS and RCS,
install the 24V wiring as a NEC Class I wiring system.
Figure 73: RFS and RCS Interconnecting Control Wiring
Main control panel
24V field terminal
block (TB2)
Control wiring raceway
cover (remove for access
to harness from main control
box to unit-mounted
control devices)
TB5
24V
115V
PB4/DS4P
Condenser
control
panel
DS2
PB1/DS1
TB4
Main
RFS Unit
RCS Unit
control
panel