IM 926-3 • ROOFPAK APPLIED SYSTEMS 50 www.DaikinApplied.com
Electrical Installation
Electrical Installation
Field Power Wiring
DANGER
Hazardous voltage. Can cause severe injury or death.
Disconnect electric power before servicing equipment. More
than one disconnect may be required to de-energize the unit.
CAUTION
Wires are located in base rail. Move wires before drilling hole
through base rail.
CAUTION
Provide proper line voltage and phase balance. Improper line
voltage or excessive phase imbalance constitutes product
abuse. It can cause severe damage to the unit’s electrical
components.
Wiring must comply with all applicable codes and ordinances or
in the absence of local codes, with the National Electrical Code
ANSI/NFPA 70 and/or Canadian Electrical Code CSA C22.1.
The warranty is voided if wiring is not in accordance with these
specifications. An open fuse, tripped circuit breaker, or Manual
Motor Protector (MMP) indicates a short, ground, or overload.
Before replacing a fuse, circuit breaker, MMP, or restarting a
compressor or fan motor, identify the trouble and correct.
According to the
means shall be located within sight of and readily accessible
from the air conditioning equipment. The unit can be ordered
with an optional factory mounted disconnect switch. This switch
is not fused. Power leads must be over-current protected at
the point of distribution. The maximum allowable overcurrent
protection (MROPD) appears on the unit nameplate.
All RPS, RFS, and RDT
All units are provided with internal power wiring for single or
dual point power connection. The power block or an optional
disconnect switch is located within the main control panel. Field
power leads are brought into the unit through 3" knockouts
in the bottom of the main control panel. Refer to the unit
nameplate to determine the number of power connections. See
If the unit has a factory mounted disconnect switch, generally
the switch must be turned OFF to open the main control panel
door. However, the door can be opened without disconnecting
power by following the procedure covered on
. If this
is done, use caution since power is not removed from the unit
or the controller.
NOTE:
To wire entry points, refer to certified drawings for
dimensions.
The preferred entrance for power cables is through the bottom
knockouts provided on the unit. If side entrance is the only
option, a drilling location is provided.
Follow the drilling dimensions exactly to prevent damage to the
control panel. The dimensions provided are the only possible
point of side entrance for the power cables.
Figure 67: RPS/RDT and RFS Power Wiring Connections
Figure 68: Optional Side Power Wiring Entrance
RCS Units
Field power wiring is connected from the main control panel in
the RFS unit to power block (PB4) or an optional disconnect
switch (DS4) located in the condenser control panel of the RCS
unit. Power leads enter the bottom left corner of the condenser
control panel through the conduit hubs shipped with the unit.
.
Electric heat
control panel
Optional
disconnect
(DS3)
3" power
knockouts
Optional
disconnect (DS2)
3" power
knockouts
Main disconnect (DS1)
or power block (PB1)