background image

13

English

10. TEST RUN

This unit is equipped with a crank case heater to ensure smooth 
startup. Be sure to turn the power on at least 6 hours before 
operation in order to have power running to the crank case 
heater.

WARNING

When leaving the unit with the power on, be sure to 
switch with another person doing the installation or 
close the front panel.

Precautions before turning the power on

• Using insulating sheets, tape electric parts as described in the 

“Cautions on Service” plate

 on the back of the front panel.

• All indoor units connected to the outdoor unit operate automati-

cally. 
Complete work on the indoor units in order to ensure maximum 
safety.

10-1 Power On–Check Operation

• Make sure to perform the check operation after installation. 

(If the air conditioner is operated using the indoor remote control-
ler without performing the check operation, the malfunction code 
“U3” is displayed in the indoor remote controller, and normal oper-
ation is disabled.)

• When making settings on the outdoor unit PC board (A2P) after 

turning the power on, do not touch anything other than the push-
button switches and dip switches. 
(See the 

“Cautions on Service” plate

 for the locations of the 

push-button switches (BS1-5) and dip switches (D1-1, 2) on the 
PC board (A2P).)

• During the operation, monitor the outdoor unit operation status 

and check for any incorrect wiring.

<Precautions During Check Operation>

If operation is performed within 12 minutes of BP units and 
outdoor units being turned on, H2P will light up, and the 
compressor will not run.

Only perform operation after checking that the LED display is as 
shown in “

10-1 Power On–Check Operation

” 2. table.

• In order to ensure uniform refrigerant distribution, it may take up to 

around 10 minutes for the compressor to start up after the unit 
begins running. This is not a malfunction.

• Each indoor unit cannot be checked individually for problems.

After this operation is complete, run the unit normally using the 
remote controller.

• The check run cannot be performed in recovery or other modes.
• If the outlet pipe thermistor (R2T), the intake pipe thermistor 

(R3T), and the pressure sensors (S1NPH and S1NPL) are 
removed before operation, the compressor might burn out, so 
avoid this under all circumstances.

10-2 Temperature control operation checklist

• After check operation is complete, checking the temperature con-

trol using normal operation.
(Heating is not possible if the outdoor temperature is 75°F (24°C)  
or higher. See the included operation manual.)
(1) Make sure the indoor and outdoor units are operating nor-

mally.
(If liquid compression by the compressor or other abnormal 
noises can be heard, stop the unit immediately, heat the 
crank case for a sufficient amount of time, and try again.)

(2) Run each indoor unit one at a time and make sure the corre-

sponding outdoor unit is also running.

(3) Check to see if cold (or hot) air is coming out of the indoor 

unit.

(4) Press the fan direction and fan strength buttons on the indoor 

unit to see if they operate properly.

<Precautions during temperature control checks>

• For around 5 minutes after the compressor stops, the compressor 

will not run even if the “operate/stop” button on the remote control-
ler is pressed.

• When the system operation is stopped by the remote controller, 

the outdoor units may continue operating for further 1 minutes at 
maximum.

• Malfunction code “U3” is displayed if check operation is not per-

formed using the test run button the first time after installation. 
Perform the check operation in accordance with “

10-1 Power On–

Check Operation

”.

[Indoor unit displays malfunction sign]
(Check on a remote controller connected to the indoor unit. 
For details. see the operation manual which comes with indoor unit.)

1. Close the outdoor unit’s front panel.

Turn the power

 on for the outdoor 

unit and the BP unit.

2. • Open the outdoor unit’s front panel.

• Make sure the LED display on the outdoor unit’s PC boards (A1P and 

A2P) are as shown in the following chart.

LED display 
(Default status 
before delivery)

SEVICE 
MONITOR

MODE

HAP

A1P

A2P

H1P

H2P

H3P

H4P

H5P

H6P

H7P

TEST/
HWL

IND MASTER SLAVE L.N.O.P DEMAND

6. Close the outer panel of the outdoor unit after check operation is complete.

Do not leave any stop valve closed 
otherwise the compressor will fail.

Caution

Be sure to turn the power on at least 
6 hours before operation in order to have 
power running to the crank case heater.

To avoid the risk of electric shock, do not touch anything other than the 
push-button switches on the PC board (A2P) when making settings.

Caution

LED display:     OFF      ON      Blinking

Use caution to avoid electric shock while 
working, since the outdoor unit is on.

• Only set the push-button switches (BS1-5) 

after making sure the microcomputer OK 
monitor is lit up.

• See the 

“Cautions on Service” plate

 on the 

front panel of the outdoor unit for details on 
how to make the settings. 
(Do not forget to write the settings down on 
the 

“Cautions on Service” plate

.)

• The dip switch (DS1-1) does not need to be 

set, so do not touch it. 
Doing so may cause malfunction.

• If you have to leave the outdoor unit during 

check operation, either switch with another 
worker or close the front panel. 

• The system operates for about 30 minutes (60 

minutes at maximum) and automatically stops 
the check operation.

The system can start normal operation about 
3 minutes 

after the check operation if

 the 

remote controller does not display any error 
code.

3. • When the customer requests

quiet operation or demand
operation, make these settings
using the push-button switches
(BS1-5) on the outdoor unit’s
PC board (A2P).

• Operate the push-button

switches through the opening
after protecting it with an
insulation cover. 
(See the 

“Cautions on Service”

plate

 for details.)

4. • Check that the liquid and gas-side

stop valves are open, and if
they are closed, open them.

5. Press the test run button (BS4) for

at least 5 seconds and perform
check operation. 
For details, see “check operation
procedure” on the 

“Cautions on

Service” plate

.

Malfunc-

tion code

Installation error

Remedial action

E3

The stop valve of an out-
door unit is left closed.

Open the gas-side stop valve and the 
liquid-side stop valve.

Refrigerant overcharge.

Recalculate the required amount of 
refrigerant from the piping length and 
correct the refrigerant charge level by 
recovering any excessive refrigerant 
with a refrigerant recovery machine.

E4

The stop valve of an out-
door unit is left closed.

Open the gas-side stop valve and the 
liquid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant 
charge has been finished correctly.

Recalculate the required amount of 
refrigerant from the piping length and 
add an adequate amount of refrigerant.

F3

Refrigerant overcharge.

Recalculate the required amount of 
refrigerant from the piping length and 
correct the refrigerant charge level by 
recovering any excessive refrigerant 
with a refrigerant recovery machine.

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the 
liquid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant 
charge has been finished correctly.

Recalculate the required amount of 
refrigerant from the piping length and 
add an adequate amount of refrigerant.

01_EN_3P329623-1.fm  Page 13  Friday, November 9, 2012  6:50 PM

Содержание RMXS48LVJU

Страница 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Страница 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Страница 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Страница 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Страница 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Страница 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Страница 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Страница 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Страница 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Страница 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Страница 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Страница 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Страница 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Страница 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Страница 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Страница 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Страница 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Страница 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Страница 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...

Отзывы: