Troubleshooting for Outdoor Unit
Troubleshooting
204
7.19 Inverter Compressor Abnormality
Error Code
L5
Method of Error
Detection
The error is detected from current flowing in the power transistor.
Error Decision
Conditions
When an excessive current flows in the power transistor
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defective compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defective main PCB (A1P)
Troubleshooting
Note:
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
Disconnect the connection
between the compressor
and the main PCB. Turn the
power transistor check
mode setting ON in setting
mode 2.
Is the
compressor's coil
disconnected or the
insulation is
defective?
There is
instantaneous power
failure.
Is inverter
output voltage
balanced? (Normal if
within
±
5V. Must be
measured when
frequency is
stable.)
Inspect the compressor
according to the diagnosis
procedure for odd noises,
vibration and operating
status of the compressor.
(R19190)
Replace the compressor.
YES
Correct power supply.
YES
Replace the main PCB
(A1P).
Not balanced
NO
Balanced
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...