Troubleshooting for Outdoor Unit
SiUS181305E
193
Troubleshooting
7.8
Refrigerant Overcharged
Error Code
F6
Method of Error
Detection
Excessive charging of refrigerant is detected during check operation by using outdoor temperature,
outdoor heat exchanger temperature, and liquid pipe temperature.
Error Decision
Conditions
When the amount of refrigerant, which is calculated during check operation by using outdoor
temperature, outdoor heat exchanger temperature, and liquid pipe temperature, exceeds the
standard.
Supposed
Causes
Refrigerant overcharge
Incorrect installation of outdoor temperature thermistor, outdoor heat exchanger thermistor,
liquid pipe thermistor (R1T, R4T, R7T)
Defective outdoor temperature thermistor, outdoor heat exchanger thermistor, liquid pipe
thermistor (R1T, R4T, R7T)
Troubleshooting
Refer to Thermistor Resistance / Temperature Characteristics table 1 on page 224.
Remove the outdoor
temperature thermistor,
outdoor heat exchanger
thermistor, liquid pipe
thermistor from the outdoor
PCB and measure the
resistance with a tester.
Check the mounting condition
of the outdoor temperature
thermistor, outdoor heat
exchanger thermistor, liquid
pipe thermistor.
Are the thermistors
installed on pipes
correctly?
Is the
characteristic of the
thermistors normal?
Correct the amount of
refrigerant.
(R13024)
Install the thermistor
correctly.
NO
Replace the defective
thermistor.
NO
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...