Troubleshooting for Branch Provider (BP) Unit
SiUS181305E
179
Troubleshooting
6.4
Signal transmission Error between Indoor Unit and
Branch Provider (BP) Unit
Error Code
U4
Method of Error
Detection
The data received from the BP unit in signal transmission is checked whether it is normal.
Error Decision
Conditions
When the data sent from the BP unit cannot be received normally, or when the content of the data
is abnormal.
Supposed
Causes
Defective BP unit PCB
Defective indoor unit PCB
Signal transmission error due to wiring error
Signal transmission error due to disturbed power supply waveform
Signal transmission error due to breaking of connection wires (wire No. 2).