Field Settings
SiUS181305E
111
Test Operation and Field Settings
2.2.3 When 2 Units are Installed in 1 Room
Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless
remote controller can be set for different address.
Both the indoor unit PCB and the wireless remote controller need alteration.
The method of address setting varies depending on the type of indoor unit and the series of wired
remote controller. Refer to the following pages for the appropriate indoor unit and wireless remote
controller.
CTXS/FTXS
Series
(1) Remove the front grille.
(2) Remove the electrical box.
(3) Remove the shield plate of the electrical box.
(4) Cut the address setting jumper JA on the PCB.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
CTXS07LVJU
CTXS07JVJU, CTXS09/12HVJU
FTXS15/18/24LVJU
ADDRESS
JC
JA
JB
ADDRESS:JA
EXIST
1
CUT
2
(R17375)
Address
JA
JB
JC
Address
JA
EXIST
1
CUT
2
(R17414)
(R9665)
ADDRESS
JC
JA
JB
ADDRESS:JA
EXIST
1
CUT
2