ELECTRICAL DATA
RKS+FTKS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTKS50BVMB
RKS50BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
6.92
53
0.18
40
0.16
3D040876
RKS+FTKS60B
RKS+FTKS71B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTKS60BVMB
RKS60BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
8.86
53
0.24
43
0.16
FTKS71BVMB
RKS71BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
16.8
20
80
10.58
53
0.26
43
0.18
3D040877
RKS+FVKS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FVKS50BVMB
RKS50BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
76
7.04
53
0.18
14+14
0.31
3D040876
RKS+FLKS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FLKS50BVMB
RKS50BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
75
7.00
53
0.18
34
0.54
3D040876
RKS+FFQ50B
RKS+FFQ60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FFQ50BV1B
RKS50BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
7.43
53
0.18
55
0.7
FFQ60BV1B
RKS60BVMB9
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
85
8.45
53
0.24
55
0.7
3D041020
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency(Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the requested
product type’’ and ’’English’’ from the drop down lists, click the search
button.
Finally, click on the document title of your choice.
•
Pair Application, Inverter Controlled Unit
•
R-410A
•
RKS50-60-71BVMB9
2
Specifications
1
2
4
•
Split - Sky Air
•
Outdoor Units