Troubleshooting
Service Diagnosis
90
4.8.2 42/50 Class
Remote
Controller
Display
E1
Method of
Malfunction
Detection
Detection within the program of the microcomputer
Malfunction
Decision
Conditions
The program of the microcomputer is in abnormal running order.
Supposed
Causes
Defective outdoor unit PCB
Noise
Momentary fall of voltage
Momentary power failure
Troubleshooting
42 class
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
YES
YES
NO
(R12188)
YES
NO
Replace the outdoor unit
PCB.
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB.
Replace the harness.
Check to see if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
NO
Replace the connecting wires
between the indoor and
outdoor units.
Check the voltage between No.1
and No.2 on the outdoor terminal
board.
Is it normal?
Is the harness
broken?
Turn on the power again.
∗
Before you check the LED A,
cancel the standby electricity
saving function by operating
fan operation with the remote
controller.
∗
Wait at least for 7 sec. after
turning on the power.