Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop forced cooling operation.
How to force cooling operation mode
■
Using the outdoor unit forced cooling operation switch
1) Push on “ ” with a screwdriver. The unit will start operating.
2) The forced cooling mode is selected, and terminates in approx. 15 minutes.
■
Using the indoor unit operation/stop button
Press the indoor unit operation/stop button for at least five seconds. (Operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To force a test run to stop, press the indoor unit operation/stop button.
■
Using the main unit’s remote control
1) Press the “operation/stop” button.
(Operation will start.)
2) Press the temperature
button and the “operation select” button at the same time.
3) Press the “operation select” button twice.
(
will be displayed and the unit will enter test run mode.)
4) Press the “operation select” button to return the operation mode to cooling.
• Test run mode will stop automatically after around 30 minutes. To force a test run to stop, press the operation/stop button.
CAUTION
1) When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
2) After closing the liquid stop valve, close the gas stop valve within three minutes, then stop the forced operation.
Facility Setting
(RKS20/25/35E2V1B only)
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in
a residence or office (the space where there is a human).
1) Cutting jumper8 (J8) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor
temperature drops below –20°C and start back up once the temperature rises again.
CAUTION
1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4) Cutting jumper 8 (J8) sets the indoor fan tap to the highest position. Notify the user about this.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
1
2
3
Push
here
Power supply
terminal block
Screwdriver
1
2
3
PCB
J1
J3
J4
J5
J6
J7
J8
S80
S80
S90
S70
Cut J8 with nippers
or a similar tools.
01_EN_3P192882-1C.fm Page 8 Tuesday, March 6, 2007 4:53 PM