background image

Si001555EC

Electrical Box

Removal Procedure

9

9

Pull out the clamp (Hole 
No.15) and disconnect 
the connector [S90].

[S90]: thermistors

10 Pull out the 3 clamps 

(Hole No.3, 7, and 13).

11 Pull out the clamp from 

the Hole No.14 and 
release the outdoor 
temperature thermistor 
harness from the slit.

12 Remove the outdoor 

temperature thermistor.

The design of the outdoor 
temperature thermistor 
varies depending on the 
model.

Step

Procedure

Points

[S90]

Clamp

(R21999)

Clamp

(R21969)

Outdoor temperature 
thermistor harness

Slit

Clamp

(R21970)

Outdoor temperature
thermistor

(R20927)

Содержание RK18NMVJU

Страница 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Inverter Pair Type 15000 18000 24000 Btu h Class Si001555EC...

Страница 2: ...Manual Removal Procedure Outdoor Unit Cooling Only Heat Pump RK18NMVJU RX18NMVJU RK24NMVJU RX24NMVJU RKN24NMVJU RX15QMVJU RX18QMVJU RX15RMVJU RX18RMVJU RX18RMVJU9 RX24RMVJU RXN18NMVJU RXN24NMVJU RXL1...

Страница 3: ...tor 4 3 Electrical Box 7 4 PCB 11 5 Thermistor ASSY Partition Plate 14 6 Sound Blankets 17 7 Electronic Expansion Valve Four Way Valve 19 8 Compressor 22 Note The illustrations may be slightly differe...

Страница 4: ...turning off all power supplies before disassembling work Step Procedure Points 1 Remove the 6 screws and remove the top panel 2 Remove the 8 screws of the front panel 3 Slide the fan motor fixing fra...

Страница 5: ...4 5 Unfasten the 2 hooks on the right side Remove the front panel 6 Remove the 4 screws of the discharge grille 7 Unfasten the 2 hooks and remove the discharge grille Step Procedure Points Hook Front...

Страница 6: ...or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the drip proof cover 2 Remove the 2 screws of the terminal cover 3 4 Open the terminal cover and p...

Страница 7: ...side of the electrical box 7 Release the fan motor lead wire from the groove and unfasten the 2 hooks When reassembling fit the fan motor lead wire into the slit at the back of the fan motor fixing fr...

Страница 8: ...rame When reassembling fit the 2 lower hooks into the bottom frame 10 Unfasten the 3 hooks on the fan motor fixing frame and release the fan motor lead wire 11 Remove the 4 screws and remove the fan m...

Страница 9: ...disconnect the connecting wire and power supply wire Loosen the 2 nuts of the conduits and remove the connecting wire and power supply wire 3 Remove the 2 screws and remove the conduit mounting plate...

Страница 10: ...d wires into the appropriate holes 1 S90 Hole No 15 14 13 7 3 2 S40 Hole No 16 2 3 S20 Hole No 11 4 S80 Hole No 1 6 Disconnect the connector S20 and pull out the clamp Hole No 11 S20 electronic expans...

Страница 11: ...ll out the clamp from the Hole No 14 and release the outdoor temperature thermistor harness from the slit 12 Remove the outdoor temperature thermistor The design of the outdoor temperature thermistor...

Страница 12: ...ical Box Si001555EC 10 Removal Procedure 13 Disconnect the relay connector for compressor 14 Remove the screw and remove the electrical box Step Procedure Points Relay connector R21971 Electrical box...

Страница 13: ...or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove the screw of the terminal board 2 Remove the earth ground screw 3 Pull out the clamp 1 and cut th...

Страница 14: ...1 Hole No 5 pull out the clamp 2 Hole No 12 and release the relay harness from the hook 6 Remove the 3 screws of the mounting plate for terminal board Step Procedure Points Earth ground screw R21976...

Страница 15: ...i001555EC PCB Removal Procedure 13 7 Remove the 7 screws of the PCB 8 Unfasten the key hook and then the other 5 hooks 9 Remove the PCB Step Procedure Points PCB R20935 Hook Key hook R21997 PCB R20937...

Страница 16: ...ff all power supplies before disassembling work Step Procedure Points 1 Remove the right side panel 1 Remove the screw of the stop valve cover 2 Slide the stop valve cover downward and remove it When...

Страница 17: ...e the clip for the thermistor 1 Cut the clamp and pull out the outdoor heat exchanger thermistor 2 Open the sound blanket top and detach the discharge pipe thermistor Be careful not to lose the fixtur...

Страница 18: ...rmistor ASSY 3 Remove the partition plate 1 Pull out the clamp 2 Remove the 2 screws and remove the partition plate When reassembling fit the lower hook into the bottom frame Step Procedure Points The...

Страница 19: ...f all power supplies before disassembling work Step Procedure Points 1 Remove the sound blanket back Since the piping ports are torn easily remove the sound blanket carefully 2 Remove the sound blanke...

Страница 20: ...ets Si001555EC 18 Removal Procedure 4 Remove the sound blanket inner When reassembling fit the sound blankets in the following order 1 inner 2 outer 3 back 4 top Step Procedure Points Sound blanket in...

Страница 21: ...askets affected by heat Keep below 120 C 248 F For the sake of this wrap the four way valve with wet cloth and provide water so that the cloth does not dry Note Before working make sure that the refri...

Страница 22: ...coil The cooling only models have no four way valve coil 3 Remove the terminal cover 4 5 Remove the protection bushing Disconnect the compressor lead wires and the overload protector Step Procedure P...

Страница 23: ...arts and remove the electronic expansion valve Heat up the 4 brazed parts and remove the four way valve When reassembling make sure that the four way valve is not inclined The cooling only models have...

Страница 24: ...estore the piping by non oxidation brazing Note Before working make sure that the refrigerant gas is empty in the circuit Be sure to apply nitrogen replacement when heating up the brazed part Do not u...

Страница 25: ...brazed part of the discharge side pipe and disconnect it Heat up the brazed part of the suction side pipe and disconnect it Remove the 3 nuts Lift up the compressor and remove it Step Procedure Point...

Страница 26: ...ersion Revised contents 06 2015 Si001555E First edition 01 2016 Si001555EA Model addition RXL15QMVJU 08 2018 Si001555EB Model addition RX15QMVJU RX18QMVJU RX15RMVJU RX18RMVJU RX24RMVJU 08 2019 Si00155...

Страница 27: ...sories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorized parts and accessories or improper installation of parts and ac...

Отзывы: