38
Resetting
Check the nature of the malfunction on the basis of the malfunction codes under par. 8.1 and if
possible, resolve the cause of the malfunction before resetting the unit.
If a locking malfunction is indicated by means of a flashing LED above the button and a
number on the display, the unit can be restarted by pressing the reset button.
7.2
Parameter settings via the service code
The parameters of the burner relay have been configured in the factory in accordance with the
following table.
These parameters can only be changed with the service code. Take the following actions to
activate the program memory:
1.
Press the
and the button simultaneously, until a
0
appears on the service display and a
0
on the temperature display.
2.
Use the button to enter
15
(service code) on the temperature display.
3.
Use the
button to set the parameter you wish to configure, on the service display.
4.
Use the and button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the button until
P
appears on the service display.
The burner relay has now been reprogrammed.
Note
Pressing the button will take you out of the menu without saving the parameter changes.
Example: Changing boiler from combi to 'hot domestic water only'
1.
Press the
and the button simultaneously.
2.
Use the button to go to
15
.
3.
Press the
button 1 x. A 0 and a 1 will appear on the display.
4.
Use the button to change the 0 to 2.
5.
Press the button until
P
appears.
6.
The change has now been implemented. The unit will only respond to a hot water request.
Para
RHOBG*AAV1
meter Setting
12
18
Description
0
Service code
[15]
-
-
Access to installers settings, the service code must be entered
(=15)
1
Installation type
1
1
0= combi
1= heating and domestic hot water via external storage tank
2= domestic hot water only
3 = heating only
2
CH pump continuous
0
0
0= post-running pump only
1= pump continuously active
2-3-5= not active
3
Set maximum CH power
99
85
Setting range value parameter c up to 85%
3.
Max. capacity modulating CH pump
80
80
Setting range value parameter c. up to 100%
4
Set maximum hot water power
80
80
Setting reach set value parameter d up to 100% (=99 + 1x )
5
Min. flow temperature of the heat line
25
25
Setting reach 10°C to set value parameter 5
5.
Max setting value supply water temperature
via operating panel
90
90
Setting reach 30°C to 90°C
6
Min.outdoor temperature of the heat line
-7
-7
Setting reach -30 to 10°C
7
Max. outdoor temperature of the heat line
25
25
Setting reach 15°C to 30°C
8
CH pump post-running time after CH
operation
1
1
Setting reach 0 to 15 minutes
9
CH pump post-running time after heating an
external DHW tank
0
0
Setting reach 0 to 15 minutes
(n/a for Combi unit)
A
Setting three-way valve
0
0
0= powered during CH operation
1= powered during hot water operation and rest
2= three-way valve in CH setting if device not in rest
3= zone regulation
4 and higher = Not active
b
Booster
0
0
No active
C
Step modulation
1
1
0= step-by-step modulation off during CH operation
1= step-by-step modulation on during CH operation
c
Minimum rpm CH
30
30
Settings reach 20 – 50%
c.
Minimum capacity modulating CH pump /
Activation external power saving switch
40
40
Setting range 0,15 – (value parameter c. )
0 = external power saving switch activated
Содержание RHOBG12AAV1
Страница 1: ...ROTEX 4P381271 88527701 02 2016 4P381271 88527701 02 2016...
Страница 29: ...30...
Страница 80: ...30...
Страница 132: ...31...
Страница 184: ...31...
Страница 236: ...31...
Страница 287: ...ROTEX Heating Systems GmbH 30...
Страница 339: ...30...
Страница 392: ...31...
Страница 416: ...ROTEX 008 1548899_00 88527703 05 2018...