background image

25

3P362438-9N

English

When turning on the power supply, the display flashes on and off. First 
checks of the power supply are executed (1-2 minutes).

When no trouble occurs: lighted as indicated (8-10 minutes).

Ready for operation: blank display indication as indicated.

When above situation cannot be confirmed after 12 minutes, the mal

-

function code can be checked on the indoor unit user interface and the 
outdoor unit segment display. Solve the malfunction code accordingly. 

The communication wiring should be checked at first.

 INFORMATION

Be sure to turn the power on at least 6 hours before operation in order 
to have power running to the crank case heater.

Accessing modes

BS1 is used to change the mode you want to access.

• 

Access mode 1
Push BS1 one time. Segment indication changes to:

• 

Access mode 2
Push BS1 for at least 5 seconds. Segment indication changes to:

 INFORMATION

If you get confused in the middle of the process, push BS1.
Then it returns to idle situation (no indication on segment displays: 
blank, refer to Functions of the push button switches which are located 

on the main printed circuit board (A1P) on page 24).

Mode 1

Mode 1 is used to set basic settings and to monitor the status of the 

unit (15.2. Monitoring function and field settings on page 31).

• 

Changing and access the setting in mode 1:
Once mode 1 is selected (push BS1 one time), you can select the 
wanted setting. It is done by pushing BS2. Accessing the selected 
setting’s value is done by pushing BS3 one time.

• 

To quit and return to the initial status, press BS1.

Example

:

Checking the content of parameter [1-10] (to know how many indoor 

units are connected to the system).

[A-B]=C in this case defined as: A=1; B=10; C=the value we want to 

know/monitor:

• 

Make sure the segment indication is displayed in operational default 
mode as shipped from factory.

• 

Push BS1 one time; result segment display:

Result: mode 1 is accessed.

• 

Push BS2 10 times; result segment display:

Result: mode 1 setting 10 is addressed.

• 

Push BS3 one time; the value which is returned (depending on the 

actual field situation), is the amount of indoor units which are con

-

nected to the system.
Result: mode 1 setting 10 is addressed and selected, return value is 
monitored information.

• 

To leave the monitoring function, push BS1 one time, you will return 
to the default situation when shipped from factory.

Mode 2

Mode 2 is used to set field settings of the outdoor unit and system.

• 

Changing and access the setting in mode 2:
Once mode 2 is selected (push BS1 for more than 5 seconds), you 
can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting’s value is done by pushing BS3 one 
time.

• 

To quit and return to the initial status, press BS1.

• 

Changing the value of the selected setting in mode 2:

 

- Once mode 2 is selected (push BS1 for more than 5 seconds) 

you can select the wanted setting. It is done by pushing BS2.

 

- Accessing the selected setting’s value is done by pushing BS3 

one time.

 

- Now BS2 is used to select the required value of the selected 

setting.

 

-

When the required value is selected, you can define the change 

of value by pushing BS3 one time.

 

- Press BS3 again to start operation according to the chosen value.

Example:

Checking the content of parameter [2-18] (to define the high static 

pressure setting of the outdoor unit’s fan).

[A-B]=C in this case defined as: A=2; B=10; C=the value we want to 

know/change

Make sure the segment indication is as during normal operation (de-
fault situation when shipped from factory).

• 

Push BS1 for over 5 seconds; result segment display:

Result: mode 2 is accessed.

• 

Push BS2 18 times; result segment display:

Result: mode 2 setting 18 is addressed.

• 

Push BS3 one time; the value which is returned (depending on the 

actual field situation), is the status of the setting. In the case of [2-
18], default value is 0, which means the function is not active.

Result: mode 2 setting 18 is addressed and selected, return value is 
the current setting situation.

• 

To change the value of the setting, push BS2 till the required value 

appears on the segment indication. When achieved, define the set

-

ting value by pushing BS3 one time. To start operation according to 

the chosen setting, confirm again by pushing BS3.

• 

To leave the monitoring function, push BS1 two times, you will 
return to the default situation when shipped from factory.

01_EN_3P362438-9N.indb   25

12/11/2019   2:35:59 PM

Содержание REYQ72TAYC Series

Страница 1: ...event of conflicting information the online installation instruction is to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instruc...

Страница 2: ...nnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installi...

Страница 3: ...only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil...

Страница 4: ...piping 14 8 1 Caution for brazing 14 8 2 Connecting the refrigerant piping 14 8 3 Guidelines for handling stop valve 17 9 Field wiring 18 9 1 Power circuit safety device and cable requirements 19 9 2...

Страница 5: ...Q 192 384 consists of multiple REYQ 72 168 modules as indi cated 72 96 120 144 168 REYQ72TAYC 1 REYQ96TAYC 1 REYQ120TAYC 1 REYQ144TAYC 1 REYQ168TAYC 1 REYQ192TAYC 2 REYQ216TAYC 1 1 REYQ240TAYC 2 REYQ2...

Страница 6: ...y For additional information see technical engineering data 1 4 Scope of the manual This manual describes the procedures for handling installing and connecting the VRV IV REYQ T series outdoor units T...

Страница 7: ...nough to support the weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance...

Страница 8: ...mproper installation may result in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will dist...

Страница 9: ...igure below and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A...

Страница 10: ...ions can be found in the Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carr...

Страница 11: ...tion bolts until their length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the...

Страница 12: ...ational regulations After piping work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 18 and 12 Checking of device and installation conditions on page 24 ar...

Страница 13: ...in 34 9 mm 7 3 2 Piping between refrigerant branch kits or refrigerant branch kits and Branch Selector units D Choose from the following table in accordance with the indoor unit total capacity connect...

Страница 14: ...Indoor unit capacity index Kit name for 3 pipes for 2 pipes 72 KHRP25M33H9 KHRP25M33HA KHRP26M22H9 KHRP26M22HA maximum 4 indoor units or KHRP26M33H9 KHRP26M33HA maximum 8 indoor units 72 111 KHRP26M33...

Страница 15: ...ing length from the first outdoor unit multi connection piping kit to the outdoor unit 33 ft 10 m Equivalent piping length from the first outdoor unit multi connection piping kit to the outdoor unit 4...

Страница 16: ...e as fol lows 3 8 in 9 5 mm 1 2 in 12 7 mm 1 2 in 12 7 mm 5 8 in 15 9 mm 5 8 in 15 9 mm 3 4 in 19 1 mm 3 4 in 19 1 mm 7 8 in 22 2 mm C REFNET joints G b d m B f A c D 9 H e g 6 h n F i 4 Outdoor unit...

Страница 17: ...vents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and prevents proper operation...

Страница 18: ...he burner flame Liquid pipe stop valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched pip...

Страница 19: ...of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection pip...

Страница 20: ...ally or vertically Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints h...

Страница 21: ...refer to 8 3 2 How to use the stop valve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec tr...

Страница 22: ...z f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 15 1 16 8 18 2 22 3 24 9 16 8 16...

Страница 23: ...multi system And the other units are Sub unit In this figure outdoor unit A is the Master unit Check operation in installation work onsite settings and so on are done by operating the printed circuit...

Страница 24: ...e accessory CAUTION Be sure to use crimp style terminal with insulating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated po...

Страница 25: ...OTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is op...

Страница 26: ...ze the system to 375 000 microns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to...

Страница 27: ...e front panel see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switches 3 1 2 1 Front panel 2 Inspect...

Страница 28: ...indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will re...

Страница 29: ...ing the additional refrigerant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant...

Страница 30: ...s BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 1 36 1 54 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3 8 10...

Страница 31: ...is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a sipho...

Страница 32: ...d stop valve service port open valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B 9 8 11 11 12 10 14 13 15 16 A C 7 1 Pressure reducing valve 2 Nitr...

Страница 33: ...top valves after pre charging the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this ch...

Страница 34: ...e selected time frames The second method is to enable low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption lim...

Страница 35: ...ly be effective when the optional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase...

Страница 36: ...tation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumption limitation that will be applied continuously The...

Страница 37: ...e target temperature upper limit Default value 1 Value 2 92 Te target temperature upper limit 0 L 1 M 2 H If Auto Te then use this setting to address different load pro files If the frequent operation...

Страница 38: ...ting 2 8 and 2 47 To activate the powerful comfort setting under heating opera tion change field setting 2 82 3 This setting is used in conjunction with setting 2 9 Quick Overshoot during heating oper...

Страница 39: ...D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual lo...

Страница 40: ...MATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour run elapse before reaching smoot...

Страница 41: ...ion code which is displayed on the outdoor unit will indi cate a main malfunction code and a sub code The sub code indicates more detailed information about the malfunction code The malfunc tion code...

Страница 42: ...ction R10T A1P X29A Check connection on printed circuit board or actuator J6 01 02 03 Temperature sensor malfunction R11T A7P X15A Check connection on printed circuit board or actuator 08 09 10 Temper...

Страница 43: ...iring between units Check indoor unit amount and total capacity con nected Check connection U9 01 System mismatch Wrong type of indoor units com bined R407C Mini split etc Indoor unit malfunction Chec...

Страница 44: ...Pull out junction connectors X1A X2A X3A X4A for the fan motors in the outdoor unit before starting service operation on the inverter equipment Be careful not to touch the live parts If a fan rotates...

Страница 45: ...tions and standards for the maximum allowable concentration level is required 2 1 1 Direction of the refrigerant flow 2 Room where refrigerant leak has occurred outflow of all the refrigerant from the...

Страница 46: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P362438 9N EM16A003B 1912 HT 00_CV_3P362438 9N indd 2 2019 09 12 11 44 31...

Отзывы: