• Outdoor Unit • REYQ-T
12
• VRV Systems • REYQ-T
38
12
Installation
12 - 1 Installation Method
3D079542
REYQ-T
For single unit installation
<Pattern1>
<Pattern2>
<Pattern3>
<Pattern1>
<Pattern2>
<Pattern3>
<Pattern1>
<Unit: mm>
Wall height unrestricted
Wall height
unrestricted
10 or more
300 or more
500 or more
<Front>
<Front>
<Front>
<Front>
<Front>
<Suction side>
500 or more
50 or
more
300 or more
300 or more
300 or more
10 or more
20 or more
20 or more
200 or more
200 or more
100 or more
400 or more
100 or more
100 or more
For installation in rows
For centralized group layout
NOTES
1. Heights of walls in case of Patterns 1 and 2:
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor units, take the suction side space
more broadly than the space as shown in this drawing.
2.
,IWKHDERYHZDOOKHLJKWVDUHH[FHHGHGWKHQKDQGKVKRXOGEHDGGHGWRWKHIURQWDQGVXFWLRQVLGHVHUYLFHVSDFHUHVSHFWLYHO\DVVKRZQLQWKH¿JXUHRQWKHULJKW
3.
:KHQLQVWDOOLQJWKHXQLWVPRVWDSSURSULDWHSDWWHUQVKRXOGEHVHOHFWHGIURPWKRVHVKRZQDERYHLQRUGHUWRREWDLQWKHEHVW¿WLQWKHVSDFHDYDLODEOHDOZD\VEHDULQJLQPLQGWKHQHHGWROHDYH
enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)
4.
7KHXQLWVVKRXOGEHLQVWDOOHGWROHDYHVXI¿FLHQWVSDFHDWWKHIURQWIRUWKHRQVLWHUHIULJHUDQWSLSLQJZRUNWREHFDUULHGRXWFRPIRUWDEO\
10 or more
<Front>
500 or more
10 or more
50 or more
50 or more 50 or more
<Front>
500 or more
100 or more
10 or more
400 or more
300 or more
300 or more
10 or more
10 or more
10 or more
<Front>
600 or more
20 or more
20 or more
<Front>
500 or more
<Pattern2>
100
or more
50 or more
50 or more
<Front>
500 or more
500 or more
<Front>
100 or more
100 or more
50 or
more
50 or more
10 or more
10 or more
20 or more
20 or more
<Front>
500 or more
300 or more
10 or more
10 or more
<Front>
500 or more
100
or more
50 or
more
100
or more
50 or more
100 or more
50 or more
100 or more
50 or more
<Front>
<Front>
10 or more
10 or more
10 or more
10 or more
500 or more
900 or more
20 or more
500 or more
50 or more
50 or more
50 or
more
50 or
more
20 or more
<Front>
500 or more
100 or more
600 or more
<Front>
500 or more
100 or more