technical data

Split
Sky Air

air conditioning systems

REQ-B8V3B_REQ-B8W1B

Pair Application

Содержание REQ100B8V3B

Страница 1: ...technical data Split Sky Air air conditioning systems REQ B8V3B_REQ B8W1B Pair Application...

Страница 2: ...Directory Daikin s unique position as a man ufacturer of air conditioning equip ment compressors and refrige rants has led to its close involve ment in environmental issues For several years Daikin h...

Страница 3: ...technical data Split Sky Air air conditioning systems REQ B8V3B_REQ B8W1B Pair Application...

Страница 4: ...data 9 4 Safety device settings 12 5 Options 13 6 Capacity tables 14 Cooling capacity tables 14 Heating capacity tables 18 7 Dimensional drawing centre of gravity 23 Dimensional drawing 23 Centre of g...

Страница 5: ...e mounted easily on a roof or terrace or simply placed against an outside wall Outdoor units are fitted with a scroll compressor renowned for low noise and high energy efficiency The piping connection...

Страница 6: ...780 2330 Indoor Units FBQ71B8V3B FBQ71B8V3B FBQ100B8V3B FBQ100B8V3B FBQ125B8V3B Nominal Capacity Cooling Standard kW 7 1 7 1 10 10 12 2 Heating Standard kW 8 8 11 2 11 2 14 5 Nominal input Cooling Sta...

Страница 7: ...nal Steps 3 3 3 3 3 Fan Motor Output W 65 65 90 90 85 Position Upper Motor Speed nominal Steps 3 Fan Motor Output W 65 Compressor Quantity 1 1 1 1 1 Motor Model JT90G P4V1N S JT90G YE JT125G P4V1 S JT...

Страница 8: ...stic environment For more details please refer to sound level drawings of this chapter The sound power level is an absolute value indicating the power which a sound source generates Sound values are m...

Страница 9: ...8 11 5 16 41 1 4 2 0 065 0 6 0 125 0 9 3TW26599 9A SYMBOLS MCA Min Circuit Amps TOCA Total Over Current Amps MFA Max Fuse Amps see note 7 LRA Locked Rotor Amps RLA Rated Load Amps OFM Outdoor Fan Moto...

Страница 10: ...50 400 9 6 11 8 16 48 2 4 2 0 090 0 8 0 135 1 0 3TW26619 9A SYMBOLS MCA Min Circuit Amps TOCA Total Over Current Amps MFA Max Fuse Amps see note 7 LRA Locked Rotor Amps RLA Rated Load Amps OFM Outdoo...

Страница 11: ...mps RLA Rated Load Amps OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps kW Rated motor output NOTES 1 RLA is based on the following conditions Indoor temp 27 CDB 19 0 CWB Outdoor temp 35...

Страница 12: ...ce REQ71BV3 REQ100BV3 REQ125BW1 REQ71BW1 REQ100BW1 Fan motor thermal protector Off 135 5 C On 95 15 C HPS Off 4 15 Mpa On 3 2 Mpa LPS Off 0 03 Mpa On 0 05 Mpa Max discharge temperature By thermistor a...

Страница 13: ...Outdoor Units R 410A REQ B8V3B_REQ B8W1B 1 5 Split Sky Air Outdoor Units 13 5 Options REQ71 125B Name of option Kit name REQ71B REQ100B REQ125B Central drain plug KKPJ5F180 4TW26599 1...

Страница 14: ...tdoor fan motor Caution TC and SHC are shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 SHC is ba...

Страница 15: ...Caution TC and SHC are shown by kW V3 230V 50Hz W1 400V 50Hz NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 Shows nominal capacities 3 SHC is based on...

Страница 16: ...tdoor fan motor Caution TC and SHC are shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 SHC is ba...

Страница 17: ...tdoor fan motor Caution TC and SHC are shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 SHC is ba...

Страница 18: ...oor fan motor Caution TC is shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 Capacities are based...

Страница 19: ...and SHC are shown by kW V3 230V 50Hz W1 400V 50Hz NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 Shows nominal capacities 3 Capacities are based on fol...

Страница 20: ...tdoor fan motor Caution TC is shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 Capacities are bas...

Страница 21: ...tdoor fan motor Caution TC is shown by kW V3 230 V 50 Hz W1 400 V 50 Hz NOTES 1 Ratings shown are net capacities Influence of fan motor heat is included 2 Shows nominal capacities 3 Capacities are bas...

Страница 22: ...ts 22 Outdoor Units R 410A REQ B8V3B_REQ B8W1B 6 Capacity tables 6 2 Heating capacity tables 3TW26322 15 RR RQ REQ71 125B Capacity Field piping length m Cooling Heating Capacity in function of field p...

Страница 23: ...witch box 5 Refrigerant piping intake 6 Power supply wiring intake knock hole J34 7 Control wiring intake knock hole J27 8 Drain outlet REQ71B Hole for anchor bolt 4 M12 3TW26344 1 unit mm 1 Gas pipe...

Страница 24: ...onal drawing 3TW26364 1 unit mm 1 Gas pipe connection J15 9 flare 2 Liquid pipe connection J9 5 flare 3 Service port in the unit 4 Grounding terminal M5 in switch box 5 Refrigerant piping intake 6 Pow...

Страница 25: ...Units R 410A REQ B8V3B_REQ B8W1B 1 7 Split Sky Air Outdoor Units 25 7 Dimensional drawing centre of gravity 7 2 Centre of gravity 3TW26329 5C REQ71B Model A REQ71B 267 3TW26349 5C REQ100B Model A REQ...

Страница 26: ...1 7 Split Sky Air Outdoor Units 26 Outdoor Units R 410A REQ B8V3B_REQ B8W1B 7 Dimensional drawing centre of gravity 7 2 Centre of gravity 3TW26369 5C REQ125B Model A REQ125B 390...

Страница 27: ...valve with service port 1 4 flare Solenoid valve Filter Electronic expansion valve Filter 4 way valve Compressor Receiver High pressure switch Service port 5 16 Heat exchanger Muffler One way valve On...

Страница 28: ...Blue WHT White RED Red ORG Orange YLW Yellow Switch box Outdoor Outdoor ON OFF Position of compressor terminal Wire entrance Power supply 1 50Hz 230V 2TW26336 1B REQ71 100BW1 A1P Printed circuit board...

Страница 29: ...Thermo switch M1F Q2M Thermo switch M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe RC Signal receiver circuit S1PH Pressure switch high S1LP Pressu...

Страница 30: ...0 Outdoor Units R 410A REQ B8V3B_REQ B8W1B 9 Wiring diagram 9 2 External connection diagram 4TW26329 7 REQ71 125B Field wire Symbol explication I Pair II Twin III Triple M Master S Slave 1 Earth leak...

Страница 31: ...d sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa 5 Curve for REQ71B in heating mode Measuring location discharge side 3TW26617 1 Sound pressure level dB A Octave...

Страница 32: ...ted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa 5 Curve for REQ125B in cooling mode Measuring location discharge side 3TW26637 2 REQ125B Heating Sound pressur...

Страница 33: ...TW26617 3 REQ100B Cooling Sound pressure level dB A Octave band center frequency Hz NOTES 1 Data is valid at free field condition 2 Data is valid at nominal operation condition 3 dB A A weighted sound...

Страница 34: ...ap at each difference in eight of 15m NOTE Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon or cases...

Страница 35: ...per row REQ71 125B A Non stacked installation 2 Obstacles exist in front of the air inlet B Stacked installation Legend C Multiple row installation Relation of dimensions of H A and L are shown in th...

Страница 36: ...re CDB Outdoor temp CWB Allowable range of operation warming up Model name REQ71BV3 REQ100BV3 REQ125BW1 REQ71BW1 REQ100BW1 Operation range Notes Depending on operation and installation conditions the...