background image

Installation manual

9

REQ71+10 REQ71~125B7W1B

Split System air conditioners

4PW19495-1B

E

LECTRICAL

 

WIRING

 

WORK

Precautions on electrical wiring work

Before obtaining access to terminal devices, all supply circuits
must be interrupted. 

Use only copper wires.

The wiring between the indoor unit and outdoor unit must be for
230 V.

Do not turn on the main switch until all the wiring is completed.
Make sure that the main switch has a contact separation of at
least 3 mm in all poles.

For W1
Make sure to connect power supply cables in normal phase. If
connected in reverse phase, the remote controller of the indoor
unit indicates "U1" and the equipment cannot operate. Change
any two of the three power supply cables (L1, L2, L3) to correct
phase.
If the contact in the magnetic switch should be forcibly turned on
while the equipment is inoperative, the compressor will burn out.
Never try to forcibly turn on the contact.

Never squeeze bundled cables into a unit.

Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).

Secure the electrical wiring with clamping material as shown in

figure 9

  so that it does not come in contact with the piping,

particulary on the high-pressure side.
Make sure no external pressure is applied to the terminal
connectors.

Secure the wiring in the order shown below.

1

Secure the ground wire to the shut-off valve attachment plate so
that it does not slide.

2

Secure the ground wire to the shut-off valve attachment plate
one more time along with the electric wiring and the inter-unit
wiring.

Lay the electrical wiring so that the front cover does not rise up
when doing wiring work and attach the front cover securely. 

(See

figure 9)

.

A

V3-type

B

W1-type

1

Switch box

2

Stop valve mounting plate

3

Ground

4

Power supply and ground wiring

5

Wiring between units

6

Tie-wrap 

When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knock-out hole.

(See figure 4)

A

Inside

B

Outside

1

Wire

2

Bush

3

Nut

4

Frame

5

Hose

When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knock-out hole from
cutting the wires.

Follow the electric wiring diagram for electrical wiring works.

Form the wires and fix the cover firmly so that the cover may be
fit in properly.

Precautions on wiring of power supply and inter-unit 
wiring

Use a round crimp-style terminal for
connection to the power supply
terminal board. In case it cannot be
used due to unavoidable reasons,
be sure to observe the following
instruction.
-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure below.

Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.

Over-tightening the terminal screws can damage the screws.

See the table below for tightening torques for the terminal
screws.

Refer to the installation manual attached to the indoor unit for
wiring of indoor units, etc.

Attach an earth leakage breaker and fuse to the power supply
line. 

(See figure 7)

In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.

All wiring must be performed by an authorized
electrician.

All components procured on the site and all electric
construction should comply with the applicable local
and national codes.

High voltage
To avoid electrical shock, make sure to disconnect the
power supply 1 minute or more before servicing the
electrical parts. Even after 1 minute, always measure
the voltage at the terminals of main circuit capacitors
or electrical parts and, before touching, make sure
that those voltages are 50 V DC or less.

NOTE

To persons in charge of electrical wiring work:

Do not operate the unit until the refrigerant piping is
complete. (Running it before the piping is ready will break
the compressor.)

Tightening torque (N•m)

M4

(X1M)

1.2~1.8

M5

(X1M)

2.0~3.0

M5

(EARTH)

3.0~4.0

1

Earth leakage breaker

2

Fuse

3

Remote controller

Содержание REQ-BW1

Страница 1: ...INSTALLATION MANUAL REQ71B7V3B REQ100B7V3B REQ71B7W1B REQ100B7W1B REQ125B7W1B Split System air conditioners...

Страница 2: ...4 5 6 6 3 1 2 3 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2...

Страница 3: ...ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses...

Страница 4: ...ount exceeds the limit it may cause an oxygen deficiency accident Be sure to use only the specified accessories and parts for installation work Failure to use the specified parts may result in water l...

Страница 5: ...Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conductor or telephone ground wire Electric potential may rise abnormally if...

Страница 6: ...foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the un...

Страница 7: ...elevant local and national regulations The minimal pipe thickness for R 410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is present Disch...

Страница 8: ...and new piping should be installed If the previously used model had problems with its compressor this might cause oxidized coolant oil scale residue and other adverse effects If the indoor or outdoor...

Страница 9: ...r turns It is now closed Cautions for handling the valve cover The valve cover is sealed where indicated by the arrow Take care not to damage it After operating the valve be sure to tighten the valve...

Страница 10: ...e refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so that it can...

Страница 11: ...the vacuum pump for 1 hour to 100 7 kPa vacuum drying If the system cannot be evacuated to 100 7 kPa within 2 hours repeat the operation of vacuum break and vacuum drying Then after leaving the system...

Страница 12: ...tside 1 Wire 2 Bush 3 Nut 4 Frame 5 Hose When you do not use a wire conduit be sure to protect the wires with vinyl tubes to prevent the edge of the knock out hole from cutting the wires Follow the el...

Страница 13: ...se phenomena If this happens turn off the power re check the wiring and switch the position of two of the three electrical wires If operation is not possible do not under any circumstances force the e...

Страница 14: ...hermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW SD Safety...

Страница 15: ...NOTES NOTES...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN19495 1B...

Отзывы: