3 About the units and options

Installation manual

5

8T7V1B*
VRV IV heat exchanger unit for indoor installation
4P408444-1B – 2016.04

3

About the units and options

3.1

About the compressor unit and
heat exchanger unit

The compressor unit and heat exchanger unit are intended for indoor
installation and aimed for air to air heat pump applications.

Specification

5 HP

8 HP

Maximum capacity

Heating

16.0 kW

25.0 kW

Cooling

14.0 kW

22.4 kW

Outside ambient
design temperature

Heating

–20~15.5°C WB

Cooling

–5~46°C DB

Ambient design temperature of
compressor unit and heat exchanger
unit

5~35°C DB

Maximum relative
humidity around the
compressor unit and
heat exchanger unit

Heating

50%

(a)

Cooling

80%

(a)

(a)

To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.

3.2

System layout

NOTICE

Design  of  the  system  must  not  be  done  at  temperatures
below –15°C.

d

d

c

c

a

b

VRV DX

VRV DX

VRV DX

EKEXV

AHU

d

d

1

2

1

In case of VRV DX indoor units

2

In case of VRV DX indoor units combined with an air
handling unit

a

Heat exchanger unit

b

Compressor unit

c

Refrigerant piping

d

User interface (dedicated depending on indoor unit type)

VRV DX

VRV direct expansion (DX) indoor unit

EKEXV

Expansion valve kit

AHU

Air handling unit

3.3

Combining units and options

3.3.1

Possible options for the compressor unit
and heat exchanger unit

For  more  possible  options,  see  the  installer  and  user  reference
guide.

Drain pan heater (EKDPH1RDX)

When.

  Installation  is  optional.  It  is  recommended  in  areas  where

the  outside  temperature  is  below  –7°C  for  more  than  24  hours
continuously.

Where.

 Install the drain pan heater in the heat exchanger unit.

How.

 See the installation instructions delivered with the drain pan

heater.

Filter for debris (delivered as accessory)

When.

 Installation is optional. It is recommended in places where

a  lot  of  debris  or  dirt  (example:  leafs)  can  go  into  the  suction
ducting.

Where.

 Install the filter in one of the following places:

▪ Suction opening of the heat exchanger unit

▪ Suction ducting (easier for maintenance)

How.

 See the installation instructions attached to the filter.

Pressure drop over the filter:

▪ 5 HP: 30 Pa at 60 m³/min

▪ 8 HP: 75 Pa at 100 m³/min

4

Preparation

4.1

Preparing installation site

4.1.1

Installation site requirements of the heat
exchanger unit

Service space.

 Mind the following requirements:

≥10

≥50

a

b

≥100

≥500

≥100

(mm)

a

Air suction side

b

Air discharge side

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

These  units  (compressor  unit,  heat  exchanger  unit  and
indoor  units)  are  suitable  for  installation  in  a  commercial
and light industrial environment.

NOTICE

This  is  a  class  A  product.  In  a  domestic  environment  this
product  may  cause  radio  interference  in  which  case  the
user may be required to take adequate measures.

Содержание RDXYQ8T7V1B

Страница 1: ...Installation manual VRV IV heat exchanger unit for indoor installation English Installation manual VRV IV heat exchanger unit for indoor installation RDXYQ5T7V1B RDXYQ8T7V1B...

Страница 2: ...iten befinden sich entsprechend Artikel 1 2f des PED au erhalb der Reichweite Risikoart H Siehe auch n chste Seite tel que d fini dans A et valu positivement par B conform ment au Certificat C tel que...

Страница 3: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim...

Страница 4: ...arget audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documenta...

Страница 5: ...ing units and options 3 3 1 Possible options for the compressor unit and heat exchanger unit For more possible options see the installer and user reference guide Drain pan heater EKDPH1RDX When Instal...

Страница 6: ...unit and all indoor units and between compressor unit and heat exchanger unit 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Openin...

Страница 7: ...Discharge ducting 5 2 3 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the heat exc...

Страница 8: ...NG 5 3 1 To connect the refrigerant piping to the heat exchanger unit 1 Remove the cover 2 Remove the 2 insulation pieces 3 Put a wet cloth in front of the EPS to protect the drain pan 4 Braze the liq...

Страница 9: ...F2 F1 F2 F1 F2 b X2M X2M X2M X1M A1P RKXYQ5 RDXYQ5 TO OUT D TO IN D F1 F2 F1 F2 a1 a2 a2 a F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 b a RKXYQ8 RDXYQ8 TO OUT D TO IN D F1 F2 F1 F2 8 HP 5...

Страница 10: ...iring depending on model PCB Legend for wiring diagram 5 8 HP A1P Printed circuit board main A2P Printed circuit board adapter C1 Capacitor A1P E1H Drain pan heater optional F1U Fuse F 1 A 250 V optio...

Страница 11: ......

Страница 12: ...4P408444 1 B 0000000 4P408444 1B 2016 04 Copyright 2015 Daikin...

Отзывы: