Preparing Unit for Operation
Spring Isolated Fans
WARNING
Moving machinery hazard. Can cause severe injury or death.
Before servicing equipment, disconnect power and lock off.
More than one disconnect may be required to de-energize unit.
Releasing Spring Mounts
The optional spring-mounted supply and return fans are locked
down for shipment. Hold-down fasteners are located at each
spring mount. Remove these fasteners before operating the
fans.
shows a typical spring mount. Note that the
3/8ʺ hold-down bolt securing the fan base to the unit cross
channel must be removed.
After removing the hold-down fasteners, rock the fan assembly
by hand to check for freedom of movement.
Figure 54: RDT Spring Mount Hold Down Fasteners
Figure 55: Fan Spring Mount Adjustment
Adjusting Spring Mounts
CAUTION
Do no use impact tools for field spring mount adjustments as
damage to bits or to the bolt slot may occur.
WARNING
Moving machinery hazard. Can cause severe injury or death.
Start the fans for the first time according to the “Check,
Test,and Start Procedures” on page 92. If this is not done,
equipment damage, severe personal injury, or death can
occur.
To adjust spring mount compression, perform the following:
1. Loosen the 0.625-18 UNF hex nut (
).
2. Place additional weight on the fan sled frame and use
a lever to slightly compress the spring or raise the sled.
This will allow the bolt to turn freely.
3. Place one or two drops of oil on the threads if needed.
NOTE:
The greatest friction that makes adjustment difficult,
comes from the surfaces of the top of the upper
rebound plate (
), both sides of the 0.615”
washer, and the underside of the sled. If friction is
occurring at these point, relieve the weight and oil the
friction surfaces.
4. Use a flat blade socket drive bit (1/2ʺ drive handle
recommended) and make sure that when adjusting the
slotted bolt, that the upper-rebound plate also turns. The
slot is located just above the hex nut. This action allows
the bolt to push the compression plate (
down with the lease friction occurring between the 0.625ʺ
washer and the underside of the channel.
NOTE:
If the spring compresses to far, lift the sled before
turning. If the spring does not compress enough,
place weight on the sled corner, forcing it down
before turning.
5. Re-adjust the position of the lower-rebound plate so that
the sled has at least 3/4ʺ travel and not more than 1.25ʺ
of travel.
Hold-down
fasteners
Hold-down
fasteners
* Grossly out-of-adjustment thrust restraints can affect this dimension.
Recheck after thrust restraints are adjusted.
"
4
/
1
±
"
8
/
3
with fan running
Leveling
screw
Spring
mount
assembly
Cross
channel
t
u
n
m
a
J
Fan base
Содержание RDT
Страница 60: ...IM 893 10 ROOFPAK SINGLEZONE UNITS 60 www DaikinApplied com Wiring Diagrams Figure 64 VFD Control SAF and RAF...
Страница 61: ...Wiring Diagrams www DaikinApplied com 61 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 65 VAV Control Inputs...
Страница 65: ...Wiring Diagrams www DaikinApplied com 65 IM 893 10 ROOFPAK SINGLEZONE UNITS Figure 67 Electric Heat Control...