IM 893-10 • ROOFPAK SINGLEZONE UNITS 132 www.DaikinApplied.com
M
aInTenanCe
Figure 119: Return Fan Assembly
Supply Fan Wheel-to-Funnel Alignment
If the unit is equipped with an airfoil or backward curved supply
fan, the fan wheel-to-funnel alignment must be as shown in
,
,
to obtain proper air delivery and operating clearance. If
necessary, adjustments are made as follows:
1. Verify that the fan shaft has not moved in its bearings.
2. Loosen the fan hub setscrews and move the wheel(s)
along the shaft as necessary to obtain the correct
dimension shown in
.
3. Retighten the setscrews to the torque specification
given in
. Tighten the setscrews
over the keyway first; tighten those at 90 degrees to the
keyway last.
4. Verify that the radial clearance around the fan is uniform.
Radial clearance can be adjusted by slightly loosening
the funnel hold-down fasteners, shifting the funnel as
required, and retightening the fasteners.
Figure 120: 20
ʺ
DWDI Airfoil Wheel-to-Funnel
Figure 121: 24
ʺ
DWDI Backward Curved Wheel-to-Funnel
Wheels
.18"
Funnel
9.31"
9.31"
CL
Fan
.18"
Содержание RDT