Electrical Data
Power Wiring
Table 6: RCS 06G – 20F Electrical Data
Model
RCS
06G
07G
10G
12F
15F
20F
Compressor Motor
Voltage
208/230
460-
208/230
460
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
Phase and hertz
3 – 60
Number of
compressors
1
2
Operating Current
Rated load amps
(each)
1
25
11 .8
27 .9
13 .6
32 .6
14 .8
22 .4
10 .6
7 .7
25 .0
12 .2
9 .0
33 .3
17 .9
12 .8
Locked rotor amps
(each)1
149
83
164
100
225
240
130
75
54
164
100
78
239
125
80
Condenser Fan Motors
Voltage
208/230
460
208/230
460
208/230
460
208/230
460
575
208/230
460
575
208/230
460
575
Phase
Single
Full load amps
(each)
5 .3
2 .2
5 .3
2 .2
3 .5
1 .6
2 .4
1 .4
1 .0
2 .4
1 .4
1 .0
2 .4
1 .1
0 .8
System Characteristics
Unit full load amps
2
27 .7
15 .9
30 .3
17 .5
34 .9
19 .5
49 .6
24 .0
17 .4
57 .2
28 .6
21 .0
73 .8
39 .1
28 .0
Minimum circuit
ampacity
34 .0
19 .0
37 .0
21 .0
48 .0
22 .0
56 .0
27 .0
20 .0
64 .0
32 .0
24 .0
83 .0
44 .0
32 .0
Maximum fuse size
(amps) or HACR
circuit breaker
ampacity
3
50
25
60
30
80
40
70
35
25
80
40
30
110
60
40
Disconnect size
60
30
60
30
100
60
60
30
30
100
60
60
200
60
60
NOTE:
1. Each compressor
2. Conditions at 45° suction and 95° ambient
3. Local codes take precedent over recommended fuse size
Figure 6: Control Box Example – RCS 10G Through 20F
Electrical Data
www.DaikinApplied.com
9
IM 962-4 • AIR-COOLED SPLIT SYSTEM CONDENSERS