27
2
• Split Sky Air • Outdoor Units
9
• Outdoor Units • R-410A • RR-B7
2
Specifications
2 - 4
Safety device settings
4TW26321-2B
R(Q)(R)71-125B7
Safety device Model
RQ71B7V3B
RQ100B7V3B
RR71B7V3B
RR100B7V3B
RQ71B7W1B
RQ100B7W1B
RQ125B7W1B
RR71B7W1B
RR100B7W1B
RR125B7W1B
Fan motor thermal protector
Off 135 ± 5°C
On 95 ± 15°C
HPS
Off 4.15 +0 / -0.10 Mpa
LPS
Max discharge temperature
By thermistor and software control
Overcurrent relay
By overcurrent sensor and software control
Off 0.03 +0.02 / -0.02 Mpa
On 3.2 +0.15 / -0.15 Mpa
On 0.05 +0.03 / -0.03 Mpa