3
|
Components
Service manual
89
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
2
Turn ON the power of the unit.
3
Measure the power supply voltage between the pins 1‑4 on the humidity
sensor connector CN.
Result:
The measured voltage MUST be 5 V DC.
a
a
Humidity sensor (PCB)
Is the measured power supply voltage
correct?
Action
Yes
Skip the next step..
No
Continue with the next step.
4
Measure the output voltage between between the pins 1‑4 on the connector
S600 on the indoor unit main PCB.
Result:
The measured voltage MUST be 5 V DC.
Is the output voltage on the indoor unit
main PCB correct?
Action
Yes
Replace the humidity sensor wiring
harness, see
No
Perform a check of the indoor unit main
PCB, see
102].
5
As there are no further check procedures for this component, perform a check
of the indoor unit main PCB to check if the humidity sensor needs to be
replaced. See
After complete check of the indoor unit
main PCB, is the problem solved?
Action
Yes
No further actions required.
No
Replace the humidity sensor, see
89].
3.7.2 Repair procedures
To remove the humidity sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.