Service and Maintenance 

 

A preventative maintenance schedule should be set up as 
soon  as  the  Unit  Cooler  is  installed.  The  unit  should  be 
inspected  periodically  for  proper  operation  and  buildup 
of dirt. 
 
1.

 

Inspect and clean the drain pan to ensure there is 
no  blockage.  The  drain  pan  should  be  cleaned 
regularly with warm water and neutral detergent. 
 

2.    The  cabinet  can  be  cleaned  with  water  and  neutral 

detergent. DO NOT clean the fans and fins using a water 
jet or high-pressure cleaner. 

 

3.  The evaporator coil should be checked once a month for 

proper  defrosting.  Many  variables  affect  coil  frosting 
such as room temperature, type of product being stored, 
how  often  new  product is  brought in  and  the  length  of 
time  the  door  to  the  room  remains  open.  Summer 
conditions of high humidity can cause heavier frost loads. 
It  may  be  necessary to  change  the  numbers  of  defrost 
cycles seasonally. 

 

4.    At  least  every  six  months  check  all  fan  motors.  Tighten 
motor mounting screws and fan set screws. 

 

 

Table 1: Troubleshooting Chart

 

PROBLEM 

POSSIBLE CAUSES 

CORRECTIVE ACTION 

Excessive buildup of 
frost on coil. 

 

Defrost time is too short. 

 

Extend defrost period on the 
temperature controller. 

 

Too high humidity in room. 

 

Limit access to cold room; do not keep 
doors open during stocking. 

Accumulation of ice or 
water in drain pan. 

 

Drain line plugged. 

 

Clean drain line. Make sure drain line is 
insulated properly. 

 

Drainpipe does not have slope angle. 

 

Install the drain line with slope.  

 

Indoor unit does not install in level at all 
directions. 

 

Check unit installation and align the unit 
level at all directions. 

 

Drain line does not have drain trap. 

 

Install drain line trap. 

Noise 

 

·         Resonance on the vibrating 
mounting parts. 

 

Fix the position of vibrating part 
correctly. 

 

Vibration of fan or fan mounting 
misaligned. 

 

Fix the position of fan correctly; replace 
if defective. 

Room temperature too 
high (not cold) 

 

Incorrect  setting  on  the  temperature 
controller. 

 

Correct  the  temperature  controller 
setting. 

 

The  compressor  stopped  by  alarms 
triggered on the controller.   

 

Check  the  type  of  error,  fix  the  error 
and replace the defective parts if any.  

 

Incorrect sensor temperature.  

 

Check  the  room  temperature  sensor 
location.  Ensure  it  was  not  affected  by 
other sources.  

 

Insufficient 

refrigerant 

flow 

to 

evaporator. 

 

Check  for  any  refrigerant  leakage  or 
choking on expansion valve.  Repair the 
fault and charge system if necessary. 

 

Thick frost built on evaporator coil. 

 

Defrost the coil and clean the frost. 

 

Too frequent defrosting. 

 

Reduce defrost cycle frequency. 

 

Incorrect matching of indoor capacity to 
outdoor.  

 

Review 

and 

reselect 

the 

unit 

combination. 

 

 

 

 

 

Содержание O-UC12-FEB23-3

Страница 1: ...3 Low Temperature Scan below QR code to download latest manual from Website https drm daikinmalaysia com download AIR COOLED COMMERCIAL REFRIGERATION SLIM UNIT COOLER INSTALLATION MAINTENANCE IOM NO O...

Страница 2: ...task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations WARNING Warning Risk of serious injury or death to person CAUTION Caution Da...

Страница 3: ...Wave with fins spacing 5mm copper bare tubes with nominal diameter of 10mm This fins pattern stands out for better performance of air flow and heat transfer Superheat measurement air tightness test a...

Страница 4: ...mm 12 7 12 7 Nominal capacities are rated in accordance with EN 328 SC3 wet coil condition for R404A with TD 7K Sound Pressure Level is measured at 1m away from every side of the unit and 1m below fa...

Страница 5: ...0 95 1 1 LFSLHS0300AXV1 1 1 1 0 95 1 1 TD Correction Factor To calculate cooling capacity for different temperature difference multiply the cooling capacity obtained from section 2 2 2 with respectiv...

Страница 6: ...e identified and operatives have suitable PPE Ensure the working area has adequate ventilation during brazing procedures The units contain moving machinery and electrical power hazards which may cause...

Страница 7: ...ting and ensure only superheated vapor is returned to compressor suction Adequately support all pipe work at a maximum of 2 meter intervals Pressure testing The unit cooler has been pressure tested in...

Страница 8: ...the drain fitting MUST be fitted the right way around otherwise it will not tighten against the drip tray One side of the nut has an angled recess this must be facing towards the drip tray The fittin...

Страница 9: ...with longer length as shown in below diagram Cable type and sizing must be selected for the application and the electrical installation should conform to the current local standards The power cable to...

Страница 10: ...y in room Limit access to cold room do not keep doors open during stocking Accumulation of ice or water in drain pan Drain line plugged Clean drain line Make sure drain line is insulated properly Drai...

Страница 11: ...O UC12 FEB23 3 Page 2 Wiring Diagram LFSLHS0200AXV1 LFSLHS0300AXV1...

Страница 12: ...ON MALAYSIA SDN BHD 34543 W Shah Alam Plant 11A Jalan Utas 15 7 Seksyen 15 40200 Shah Alam Selangor Malaysia Banting Plant Lot 10 Jalan Perusahaan 8 Kawasan Perusahaan Pekan Banting 42700 Banting Sela...

Отзывы: