Fan Speed Switch Operation
Fan speed is determined by manual selection from fan switch
OFF to HIGH, MEDIUM and/or LOW. In the OFF position, all
outputs are off and the display is blank.
Up/Down Arrow Operation
A first touch of either arrow will display the setpoint (a single
set point is employed for both heating and cooling). Continued
pressure on either arrow will scroll the setpoint to new values.
After three consecutive seconds on either arrow, the selected
setpoint becomes effective and the display of the room
temperature resumes.
Configuration
Table 2: Circuit Board Jumper Configuration
Jumper
Closed ON*
Open OFF
JP1
Local Sensing
Remote Sensing
JP2
2 Pipe System
4 Pipe System
JP3
Factory Use Only
JP4
0-10 VOC
Main Output
4-20 mA
Main Output
JP5
0-10 VOC
Secondary Output
4-20 mA
Secondary Output
Table 3: Dip Switch Configuration
Switch
Closed ON*
Open OFF
1
Not Use
Not Used
2
Staged Heat 3°F Diff.
(Term. 13)
Aux. Heat No Diff. (Term.
13)
3
°F Display
°C Display
4
Main & Sec. Outputs
0-10 VOC (Term. 10 &
11) requires JP4 & JP5
Main & Sec. Outputs
4-20 mA (Term. 10 & 11)
Remove JP4 & JP5
5
Operating Position
Not Used
6
Setback= 90°F & 50°F
Setback = 85°F & 60°F
Note:
* On is with the dip switch handle to the right. See diagram.
Figure 3: Circuit Board
Service Menu:
Access: Press UP▲ and DOWN▼ arrows for 5 seconds.
Menu Selection: Select 1 to 5 by pressing the mode button or
by pressing the UP▲ and DOWN▼ arrows simultaneously.
Adjust Value: Use UP▲ or DOWN▼ arrow.
Table 4: Service Functions
Item #
Function
Range
Default
1
Zone Temp Offset
-5.1 °F to 5.1 °F
°0 F
2
Valve Stroke Time 30 sec. to 5 min.
120 sec.
3
Fan Delay to OFF
2 to 10 min.
120 sec.
4
Compressor
Minimum OFF
Time
30 sec. to 10 min.
120 sec.
5
Purge Cycle
0 = time based
1 = temperature
based
1