background image

Installation and Maintenance Manual  IM 1017-1

Group: 

Applied Air Systems

Part Number: 

910102992 

Date: 

January 2017

MT 168 0-10 VDC/4-20mA Thermostat

Installation 

 

DANGER

READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING 

TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT. 
Failure to observe safety information and comply with instructions 

could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY 

DAMAGE. 
To avoid electrical shock or damage to equipment, disconnect power 

before installing or servicing. Use only wiring with insulation rated for 

full thermostat operating voltage. Use copper wire only. Insulate or 

wire-nut all un-used leads. Any wiring, including the remote probe, may 

carry the full operating voltage of the thermostat. 
To  avoid  potential  fire  and/  or  explosion  do  not  use  in  potentially 

flammable or explosive atmospheres. 
Retain these instructions for future reference. You must review your 

application and national and local codes to ensure that your installation 

will be functional and safe. 

 CAUTION

Care should be used to avoid electrostatic discharge to the 

microprocessor. 
This unit has configuration dip switches and jumpers. You may need to 

reconfigure the thermostat for your application. 

1.  Install the thermostat with the two furnished mounting 

screws to a standard 4-1/16" × 2-1/8" square device 

box with a 2" × 4" adapter ring. 

2.  For wall installations, mount the thermostat on an 

inside wall approximately 5 feet above the floor. The 

location should provide circulation at average room 

temperature. Avoid direct sunlight or sources of hot or 

cold air in the room or wall. 

3.  Remove the cover. Mount thermostat base assembly 

to the outlet box using screws provided. Tighten the 

screws evenly but do not overtighten. Connect wires 

per wiring diagram. 

4.  To use a remote sensor on units with local sensing 

capability, remove jumper JP-1 to disable local 

sensing. Failure to remove JP-1 will cause improper 

operation of thermostat. 

5.  Connecting a jumper between terminals 16 and 17 

will disable the secondary output and change the 

main output to heat mode. 

6.  Connection of a 24 VAC set-back signal will force 

the control into unoccupied mode (see diagram). 

Pressing an arrow key or the mode buttons on the 

thermostat cover will disable the setback input for 

one hour. 

7.  Remove the LCD plastic protective film to complete 

the installation. Reinstall the cover assembly. Install 

cover locking screw provided. 

8.  Checkout: After wiring and installation are complete, 

energize the system and check the operation. Adjust 

the thermostat as necessary to complete at least one 

cycle. Be sure the thermostat and all other equipment 

are functioning correctly. 

Отзывы: