Field Settings
SiSG121917E
195
Part 7 Trial Operation and Field Settings
5.2.2 Field Settings with BRC1E63 Wired Remote Controller
Outline
When an optional accessory is installed on the indoor unit, settings of the indoor unit may be
changed. Refer to the installation manual for each optional accessory.
Procedure
1
Press and hold the Cancel button
for 4 seconds or longer.
Service Settings menu is
displayed.
2
3
Highlight the Mode No., and
select desired "Mode No." by
using " " (Down/Up) button.
4
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. " - " means no
function.
5
<Basic screen>
1
Fan
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
<Service Settings menu screen>
2
Return
Setting
Service Settings
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
Group Address
Indoor unit AirNet Address
1/3
Press Menu/Enter button.
<Field settings screen>
In the case of individual
setting per indoor unit
In the case of group
setting
3
4
5
Unit No
0
1–01
5–––
9–––
2–02
6–––
3–01
7–––
Field settings
0–01
4–––
8–––
Return
Setting
Mode
20
3
5
Mode
10
Unit No
0
1–
∗
5–––
9–––
2–
∗
6–––
3–
∗
7–––
Field settings
0–
01
4–––
8–––
Return
Setting
Press Menu/Enter button.
FIRST CODE NO.
SECOND CODE NO.
Select
Field settings
in the
Service Settings menu, and
press Menu/Enter button.
Field settings screen is
displayed.
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected),
highlight the Unit No. and select
"Indoor unit No." to be set by
using " " (Down/Up) button.
(In the case of group setting, this
operation is not needed.)
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
"SECOND CODE NO." by using
" " (Down/Up) button.
Multiple identical mode number
settings are available.
In the case of group setting, all of
SECOND CODE NO. which may
be set are displayed as "
∗
".
"
∗
" is changed to SECOND
CODE NO. to be set.
And, SECOND CODE NO. " - "
means no function.
Содержание MKS-T Series
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B...