Commission Unit
www .DaikinApplied .com 23
OM 1263 • MICROTECH UNIT CONTROLLER
RF/EF Set-Up
(
See page 23 for more information)
Table 12: Return Fan/Exhaust Fan Set-up Menu
Item Display
Name
Default Setting
Range
Password Level
MaxVentSpd=
100%
0 – 100%
N/A
Max RFEF RPM=
2600
0 – 5000
2
Max RF/EF Hz=
60.0Hz
0 – 100Hz
2
CompOp_
MinSAF=
20%
10 – 100%
2
“RF/EF Status=
(EBM Fan)*”
—
OK
2
HLL
TFEI
TFM
TFE
BLK
SKF
PHA
UzLow
UzHigh
UeLow
UeHigh
NoComm
*See exhaust fan failure codes on
MaxVentSpd
is an adjustable item that sets the exhaust
fan speed when an external ventilation override input to the
exhaust fan is present .
Max RFEF RPM=
is an adjustable item that sets the maximum
RPM value for the exhaust air fan .
NOTE:
This is set based on the exhaust fan model size.
Max RF/EF Hz
is an adjustable item to allow the maximum fan
speed based on space design conditions
CompOp_MinSAF
is an adjustable minimum speed for the fan
to be running and allow for compressor operation
RF/EF Status
is a status only item that the fan motor or VFD
output on the status of the exhaust or return fan motor