Troubleshooting
SiE74-202
24
Troubleshooting
1.4
Photocatalytic Operation does not Activate
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Photocatalytic operation does not activate during equipment operation (lamp does not light).
Supposed
Causes
Faulty lamp
Faulty transformer
Faulty PCB
Troubleshooting
Check power supply voltage
between one of the pins for X9A
and X10A.
Refer the drawing next page.*
*Make sure to press the door switch
(safety switch) DS1 before
checking voltage.
Check connector and harness
connection.
Correct connection
Replace control PCB (A1P)
Replace control PCB A1P.
•
Check connector X4A and
CN1.
•
Replace wire harness
between X4A of A1P and
CN1 of A3P.
Is connection
normal?
(Z0008)
Is voltage
between 220 to 240
VAC?
Check power supply of inverter
PCB. (A3P-CN1)
Replace lamp or inverter
PCB A3P.
Check transformer secondary
voltage
(A1P-X4A).
Is voltage
higher than 12
VDC?
Is voltage
higher than 12
VDC?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
YES
YES
NO
NO
NO
YES
NO
Содержание MC401VE
Страница 1: ...SiE74 202 Air Cleaners MC401VE Service Manual MC401...
Страница 25: ...Operating Manual SiE74 202 18 Operation Manual...
Страница 32: ...SiE74 202 Troubleshooting Troubleshooting 25 Power supply voltage check...
Страница 33: ...Troubleshooting SiE74 202 26 Troubleshooting...
Страница 40: ...SiE74 202 Removal Procedure of MC401VE Removal Procedure 33 5 Remove inverter lamps Step Procedure Points...
Страница 45: ...Removal Procedure of MC401VE SiE74 202 38 Removal Procedure...
Страница 47: ...Wiring Diagram SiE74 202 40 Reference Data 1 Wiring Diagram 1 1 MC401VE 3D027638...
Страница 48: ...SiE74 202 Parts List Reference Data 41 2 Parts List 2 1 Parts Illustration MC401VE...
Страница 51: ...SiE74 202 ii Index...