P
erforManCe
d
aTa
www.DaikinApplied.com 31
IM 970-2 • MAVERICK I ROOFTOP
Table 18: Gross System Performance—MPS A04C, 4 Tons Gas Heat
Entering Indoor Air @ 80°F (26 .7°C) dbE
1
wbE
71°F (21 .7°C)
67°F (19 .4°C)
63°F (17 .2°C)
CFM
(L/s)
1650
(779)
1500
(708)
1275
(602)
1650
(779)
1500
(708)
1275
(602)
1650
(779)
1500
(708)
1275
(602)
DR
1
0 .1
0 .08
0 .05
0 .1
0 .08
0 .05
0 .1
0 .08
0 .05
Outdoor Dry Bulb
Temperature °F (°C)
75
(23.9)
Total BTUH
(kW)
60.3
(17.7)
59.3
(17.4)
57.6
(16.9)
56.1
(16.4)
55.1
(16.1)
53.6
(15.7)
51.1
(15.0)
50.2
(14.7)
48.8
(14.3)
Sens BTUH
(kW)
31.2
(9.2)
29.8
(8.7)
27.7
(8.1)
39.8
(11.7)
38.1
(11.2)
35.4
(10.4)
43.9
(12.9)
41.9
(12.3)
39.0
(11.4)
Power (kW)
2.6
2.6
2.5
2.6
2.6
2.5
2.6
2.5
2.5
80
(26.7)
Total BTUH
(kW)
58.5
(17.1)
57.4
(16.8)
55.9
(16.4)
54.2
(15.9)
53.2
(15.6)
51.8
(15.2)
49.2
(14.4)
48.4
(14.2)
47.0
(13.8)
Sens BTUH
(kW)
31.0
(9.1)
29.6
(8.7)
27.5
(8.1)
39.6
(11.6)
37.8
(11.1)
35.2
(10.3)
43.6
(12.8)
41.7
(12.2)
38.8
(11.4)
Power (kW)
2.8
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
85
(29.4)
Total BTUH
(kW)
56.7
(16.6)
55.7
(16.3)
54.2
(15.9)
52.4
(15.4)
51.5
(15.1)
50.1
(14.7)
47.5
(13.9)
46.6
(13.7)
45.3
(13.3)
Sens BTUH
(kW)
30.6
(9.0)
29.2
(8.6)
27.1
(8.0)
39.2
(11.5)
37.4
(11.0)
34.8
(10.2)
43.2
(12.7)
41.3
(12.1)
38.4
(11.3)
Power (kW)
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
90
(32.2)
Total BTUH
(kW)
55.0
(16.1)
54.0
(15.8)
52.5
(15.4)
50.7
(14.9)
49.8
(14.6)
48.4
(14.2)
45.7
(13.4)
44.9
(13.2)
43.7
(12.8)
Sens BTUH
(kW)
30.0
(8.8)
28.6
(8.4)
26.6
(7.8)
38.6
(11.3)
36.9
(10.8)
34.3
(10.0)
42.6
(12.5)
40.7
(11.9)
37.9
(11.1)
Power (kW)
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.0
95
(35)
Total BTUH
(kW)
53.3
(15.6)
52.3
(15.3)
50.9
(14.9)
49.0
(14.4)
48 .1
(14 .1)
46.8
(13.7)
44.1
(12.9)
43.3
(12.7)
42.1
(12.3)
Sens BTUH
(kW)
29.2
(8.6)
27.9
(8.2)
26.0
(7.6)
37.8
(11.1)
36 .1
(10 .6)
33.6
(9.9)
41.9
(12.3)
40.0
(11.7)
37.2
(10.9)
Power (kW)
3.3
3.3
3.3
3.3
3 .3
3.3
3.3
3.3
3.2
100
(37.8)
Total BTUH
(kW)
51.7
(15.2)
50.8
(14.9)
49.4
(14.5)
47.4
(13.9)
46.6
(13.7)
45.3
(13.3)
42.5
(12.4)
41.7
(12.2)
40.6
(11.9)
Sens BTUH
(kW)
28.3
(8.3)
27.0
(7.9)
25.2
(7.4)
36.9
(10.8)
35.3
(10.3)
32.8
(9.6)
41.0
(12.0)
39.2
(11.5)
36.4
(10.7)
Power (kW)
3.6
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
105
(40.6)
Total BTUH
(kW)
50.2
(14.7)
49.3
(14.4)
47.9
(14.0)
45.9
(13.5)
45.1
(13.2)
43.9
(12.9)
40.9
(12.0)
40.2
(11.8)
39.1
(11.5)
Sens BTUH
(kW)
27.2
(8.0)
26.0
(7.6)
24.2
(7.1)
35.8
(10.5)
34.3
(10.0)
31.9
(9.3)
39.9
(11.7)
38.1
(11.2)
35.5
(10.4)
Power (kW)
3.8
3.8
3.7
3.8
3.7
3.7
3.8
3.7
3.7
110
(43.3)
Total BTUH
(kW)
48.7
(14.3)
47.8
(14.0)
46.5
(13.6)
44.4
(13.0)
43.6
(12.8)
42.5
(12.4)
39.5
(11.6)
38.8
(11.4)
37.7
(11.1)
Sens BTUH
(kW)
26.0
(7.6)
24.8
(7.3)
23.1
(6.8)
34.6
(10.1)
33.1
(9.7)
30.8
(9.0)
38.7
(11.3)
36.9
(10.8)
34.4
(10.1)
Power (kW)
4.0
4.0
3.9
4.0
4.0
3.9
4.0
4.0
3.9
115
(46.1)
Total BTUH
(kW)
47.3
(13.9)
46.5
(13.6)
45.2
(13.2)
43.0
(12.6)
42.3
(12.4)
41.1
(12.0)
38.1
(11.2)
37.4
(11.0)
36.4
(10.7)
Sens BTUH
(kW)
24.6
(7.2)
23.5
(6.9)
21.8
(6.4)
33.2
(9.7)
31.7
(9.3)
29.5
(8.6)
37.3
(10.9)
35.6
(10.4)
33.1
(9.7)
Power (kW)
4.3
4.2
4.2
4.3
4.2
4.2
4.3
4.2
4.2
120
(48.9)
Total BTUH
(kW)
46.0
(13.5)
45.2
(13.2)
43.9
(12.9)
41.7
(12.2)
41.0
(12.0)
39.8
(11.7)
36.7
(10.8)
36.1
(10.6)
35.1
(10.3)
Sens BTUH
(kW)
23.0
(6.7)
22.0
(6.4)
20.5
(6.0)
31.6
(9.3)
30.2
(8.9)
28.1
(8.2)
35.7
(10.5)
34.1
(10.0)
31.7
(9.3)
Power (kW)
4.5
4.5
4.4
4.5
4.5
4.4
4.5
4.5
4.4
125
(51.7)
Total BTUH
(kW)
44.7
(13.1)
43.9
(12.9)
42.7
(12.5)
40.4
(11.8)
39.7
(11.6)
38.6
(11.3)
35.5
(10.4)
34.8
(10.2)
33.9
(9.9)
Sens BTUH
(kW)
21.3
(6.2)
20.3
(6.0)
18.9
(5.5)
29.9
(8.8)
28.6
(8.4)
26.6
(7.8)
34.0
(10.0)
32.4
(9.5)
30.2
(8.8)
Power (kW)
4.8
4.8
4.7
4.8
4.8
4.7
4.8
4.7
4.7
Note:
DR — Depression Ratio; dbE — Entering Air Dry Bulb; wbE — Entering Air Wet Bulb; Total — Total Capacity × 1000 BTUH; Sens — Sensible Capacity × 1000 BTUH Power–KW input
1. When the entering air dry bulb is other than 80°F (27°C), adjust the sensible capacity from the table by adding (1.10 × CFM × (1 – DR) × (dbE – 80))
Содержание Maverick I MPS A03C
Страница 21: ...Wiring Diagrams www DaikinApplied com 21 IM 970 2 MAVERICK I ROOFTOP Figure 23 Wiring Diagram MPS A05C...
Страница 51: ...Maintenance www DaikinApplied com 51 IM 970 2 MAVERICK I ROOFTOP Figure 42 System Charge Chart MPS A04C Cooling...
Страница 52: ...IM 970 2 MAVERICK I ROOFTOP 52 www DaikinApplied com Maintenance Figure 43 System Charge Chart MPS A05C Cooling...
Страница 54: ...IM 970 2 MAVERICK I ROOFTOP 54 www DaikinApplied com Maintenance Figure 46 Speed Tap Examples...
Страница 59: ......