18 Troubleshooting
Installation and operation manual
39
LRYELRNUN5A7Y1
CO
₂
Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
Main code
LRYEN10*
LRNUN5*
Cause
Solution
O
O
▪ Heat exchanger of outdoor unit is blocked.
▪ The outdoor temperature is above the
maximum operating temperature.
▪ Check if any obstacles block the heat
exchanger and remove them.
▪ Operate
the
unit
only
within
the
temperature operation range.
O
O
Supply voltage dropped
▪ Check the power supply.
▪ Check the wiring size and length of the
power supply. They must be according to
the specifications.
O
Transmission outdoor unit – inverter: INV1/
FAN1 transmission trouble
Check connection.
O
O
Unbalanced power supply voltage
Check the power supply.
O
O
Lost phase in power supply
Check the connection of the power supply
cable.
O
O
Insufficient supply voltage
Check the power supply.
O
—
Communication error to indoor unit
Check the connection of the communication
cables upstream of indoor units (error
displayed on remote controller).
O
—
Communication error to indoor unit
Check the connection of the communication
cables downstream of indoor units (error
displayed on remote controller).
O
—
Wrong combination of indoor units
▪ Check the number of connected indoor
units.
▪ Check if an indoor unit is installed that is
not a possible combination.
O
—
Replaced all air conditioner indoor units after
confirmed communication
Check the communication cable and conduct
operation after all communication cables are
corrected.
If an air conditioner indoor unit is installed:
▪ If you have changed the power supply
cable or communication cable: turn the
outdoor unit operation switch OFF but
keep power supply ON.
▪ Then push BS3 on the A1P PCB for
more than 5 seconds.
O
—
Added any air conditioner indoor units after
confirmed communication
NOTICE
After turning ON the operation switch, wait at least 1
minute before switching off the power supply. Electrical
leakage detection is performed shortly after the
compressor starts. Switching off the power supply during
this check will result in an incorrect detection.